![Beckhoff C6640 Installation And Operating Instructions Manual Download Page 14](http://html1.mh-extra.com/html/beckhoff/c6640/c6640_installation-and-operating-instructions-manual_2719427014.webp)
Installation Instructions
Power Supply Connection with
100-240 V
AC
power supply unit
Supplied mains power unit
The Industrial PC is serially fitted with a 100-240 V
AC
, 50-60 Hz full range
power supply unit .
Current carrying capacity of
the 100-240 V power
supply unit
Output voltages from the
100-240 V power supply unit
Current loading
maximum
+3.3 V
16 A
+5 V stand by
2 A
+5 V
25 A
-5 V
0.3 A
+12 V
13 A
-12 V
0.8 A
Mains Socket
A mains socket is located on top of the PC housing next to the main switch
in order to connect the power supply.
Mains socket and main
switch at the PC housing
main switch
mains socket
Power supply cords
Power cords Europe
In the area Europe you use the provided cable with inlet connector for non-
heating apparatus to connect the Industrial-PC to the power supply.
Power cords USA / Canada
In the area USA / Canada the power supply cable must show the following
specifications according to the supply voltage:
Listed, Detachable, maximum 4.5 m (14.76 ft.) long; rated minimum 125 V,
10 A, Type SJT or Type SVT; one end terminates in NEMA 5-15P/-20P
grounding-type attachment plug, other end in appliance coupler
or
Listed, Detachable, maximum 4.5 m (14.76 ft.) long; rated minimum 250 V,
10 A, Type SJT or Type SVT; one end terminates in NEMA 6-15P/-20P
grounding-type attachment plug, other end in appliance coupler.