BC7300
25
Parameterisation Table
Parameter
x 10
x 1
Default
Parameter value
0
1..9
-
Indicates the parameter of the x 10 function
1
RTU mode
Modbus
1
2
1
ASCII mode
1
8 data bits, no parity
one stop bit
2
8 data bits even Parity
one stop bit
3
8 data bits odd Parity
one stop bit
4
7 data bits even Parity
one stop bit
5
7 data bits odd Parity
one stop bit
6
one stop bit
7
2 stop bits
8
8 data bits, no parity
two stop bits
9
8 data bits even Parity
two stop bits
10
8 data bits odd Parity
two stop bits
11
7 data bits even Parity
two stop bits
Frame
2
12
1
7 data bits odd Parity
two stop bits
1
38400 baud
2
19200 baud
3
9600 baud
4
4800 baud
5
2400 baud
6
1200 baud
7
600 baud
8
300 baud
Baud rate
3
9
3
150 baud
End of Frame Time
4
0..9
0
In ms for RTU mode (0 dependent on the baud
rate)
In seconds for ASCII mode (0 EOF time switched
off)
Watchdog 100 ms
5
0..9
0
Watchdog x 100 ms
Watchdog 1000 ms
6
0..9
1
Watchdog x 1000 ms
Factory setting
9