background image

Instruction Manual

 – Model CF2300A Oil Burner

4

Form 6104 BCF-23-R0399

Pre-installation checklist

Table 1 – Nozzle capacities at various pressures

  

Combustion air supply

• The burner requires combustion air and ventilation air for

reliable operation. Assure that the building and/or com-
bustion air openings comply with National Fire Protection
Standard for Oil-Burning Equipment, NFPA 31. For appli-
ance/burner units in confined spaces, the room must have
an air opening near the top of the room plus one near the
floor, each with a free area at least one square inch per
1,000 Btu/hr input of all fuel burning equipment in the
room. For other conditions, refer to NFPA 31 (CSA B1139-
M91 in Canada).

• If there is a risk of the space being under negative pressure

or of exhaust fans or other devices depleting available air
for combustion and ventilation, the appliance/burner
should be installed in an isolated room provided with out-
side combustion air.

  

Clearances

• With the burner installed in the appliance, there must be

adequate space in front of and on the sides of the burner to
allow access and operation. Verify that the clearance di-
mensions comply with all local codes and with the appli-
ance manufacturer's recommendations.

  

Fuel supply

• The fuel supply piping and tank must provide #1 or #2

fuel oil at pressure or vacuum conditions suitable for the
fuel unit (oil pump) on the burner. Refer to fuel unit litera-
ture in the literature envelope in the burner carton to verify
allowable suction pressure.

When fuel supply is level with or higher than burner
fuel unit —

• When the fuel unit is not required to lift the oil, the instal-

lation is usually suitable for either a one-pipe or two-pipe
oil system. The oil pressure at the inlet of the fuel unit must
not exceed 3 psig.

• The fuel unit is shipped with the 

by-pass plug

 installed.

Leave the by-pass plug installed for all low/high firing
burners, regardless whether one-pipe (with by-pass loop)
or two-pipe
. See 

Figure 8

 for installation of the by-pass

loop required for one-pipe fuel supply installations. See

Figure 9

 for connections to the fuel unit for two-pipe fuel

supply installations.

When fuel supply is below the burner fuel unit —

• Use a two-pipe oil system when the fuel unit must lift the

oil more than 8 feet if burner is equipped with a 

B

 fuel unit

— or more than 2 feet if burner is equipped with an 

H

 fuel

unit. The return line provided by the two-pipe system is
needed to purge the air from the fuel lines and minimize
the likelihood of air-related problems during operation.

❏  

Vent system

• The flue gas venting system must be in good condition

and must comply with all applicable codes.

❏  

Electrical supply

• Verify that the power connections available are correct for

the burner. All power must be supplied through fused dis-
connect switches.

❏  

Verify burner components —

Burner box

, Model CF2300A

Air tube assembly

 (selected per following)

Mounting flange kit

Pedestal mounting assembly kit

 (recommended)

Oil nozzle

, per 

Table 1

 — Use only 45° to 70° solid pat-

tern nozzles unless otherwise shown by appliance manu-
facturer.
Find the required firing rate in the 300 psig column (high
fire rate).
Select the corresponding nozzle from column 1 (Rated
gph @ 100 psig
).

Rated 
gph @ 

100 psig

Pressure - pounds per square inch

125

150

175

250

275

300

  4.50

5.04

5.51

5.95

7.11

7.46

7.79

  5.00

5.59

6.12

6.61

7.91

8.29

8.66

  5.50

6.15

6.74

7.28

8.70

9.12

9.53

  6.00

6.71

7.35

7.94

9.49

9.95

10.39

  6.50

7.27

7.96

8.60

10.28

10.78

11.26

  7.00

7.83

8.57

 9.26

11.07

11.61

12.12

  7.50

8.39

9.19

9.92

11.86

12.44

12.99

  8.00

8.94

9.80

10.58

12.65

13.27

13.86

  9.00

10.06

11.02

11.91

14.23

14.92

15.59

 10.00

11.18

12.25

13.23

15.81

16.58

17.32

 11.00

12.30

13.47

14.55

17.39

18.24

19.05

 12.00

13.42

14.70

15.87

18.97

19.90

20.78

Summary of Contents for CF 2300A

Page 1: ...ular maintenance it will provide years of trouble free service Please take a few minutes to read the section entitled To the owner inside this manual Then keep the manual in a safe place where it can...

Page 2: ...use in your heating appliance or try to light the burner by tossing burning material into the appliance This could result in severe personal injury death or substantial property damage Never attempt t...

Page 3: ...dard 296 and has listed it for use with No 1 or No 2 fuel oil as specified in ASTM D396 State and local approvals appear on the burner rating label Certified by ULC Approved by Commonwealth of Massach...

Page 4: ...The fuel unit is shipped with the by pass plug installed Leave the by pass plug installed for all low high firing burners regardless whether one pipe with by pass loop or two pipe See Figure 8 for ins...

Page 5: ...er Table 2 Tube KS 10 0 to 19 9 GPH per Table 2 Maximum firing capacity depends on the firebox pressure Use Table 2 to verify the correct air tube type for the firing rate required Use Tube KS only wh...

Page 6: ...Slide both plates completely to the left on the primary adjusting plate item g and finger tighten acorn nut d Slide the completed adjusting plate assembly over the nozzle line end Move the plate assem...

Page 7: ...d if necessary to reposition the nozzle line Once dimension Z is set do not loosen acorn nut d again For the setting of acorn nut c refer to page 12 Insert burner Position the burner in the front of...

Page 8: ...e is required for low high operation It simulates the flow of a two pipe system at the fuel unit Figures 8a and 8b are for type H fuel units Figure 8c is for a type B fuel unit Oil supply return lines...

Page 9: ...gulator The low fire by pass regulation is done in ternally for type B fuel units shown in Figure 9c Oil supply connects to one of the fuel unit Inlet ports Oil return connects to the fuel unit Return...

Page 10: ...guidelines See Figure 10 for a typical wiring diagram with R8184 oil primary for reference purposes only The CF2300A burner is available with many different wiring configurations Refer to the wiring d...

Page 11: ...operationally checked Burner has been installed in accordance with appliance manufacturer s instructions when available Also refer to appliance manufacturer s instructions when available for start up...

Page 12: ...on the air setting will be adjusted for best performance as discussed later in this manual The damper moves to high fire position as the damper rod item d rotates the damper linkage arm item f You wil...

Page 13: ...m assembly c Ball joint assembly do not adjust position of ball joint d Damper rod e Damper rod guide f Damper linkage arm sets high fire air position g Damper h Damper label position indicator for ai...

Page 14: ...ing To vent Attach a clear plastic tube to the air bleed valve Figure 8a 8b 9a or 9b as applies item p Place the end of the tube in a container to catch the oil Then loosen the fuel unit air vent valv...

Page 15: ...ncrease O2 from 2 5 to 5 5 c A margin of reserve air has been added to accommo date variable conditions 7 Check the breech draft pressure against the appliance manufacturer s recommended setting typic...

Page 16: ...embly Specify burner model and air tube length 7 Head assembly CF2300A 51203 8 Pressure regulator Not used with B pump 21319 9 Fuel lines Specify length Item Part name Description Part number 10 Dampe...

Reviews: