4
Technical data
KNX/SMI Actuator
REG-3TE 16K BT
min.
typ.
max.
Unit
Auxiliary power supply 230 V AC SMI interface
Operating voltage
198
230
253
V AC
Mains frequency
50
Hz
SMI power consumption
deactivated
--
W with
230 V AC
SMI power consumption
activated
1.3
W with
230 V AC
Power-saving relay switching
capacity for SMI drives
3600
VA
SMI outputs
Number of SMI interfaces
1
Pc
Number of motors
16
Pc
Number of groups
16
Pc
Bluetooth transceiver
Transmission frequency
2.4
GHz
Transmission power
0
dBm
Input sensitivity
-90
dBm
Operating range
(environment without inter-
ference)
5
m
KNX Interface
TP 1
Current consumption KNX
5
mA
Current consumption KNX
at device start
18
mA
Voltage
30
V DC
Conformity
Available at www.becker-antriebe.com/ce
This device meets the EMC directives for use in residen-
tial and commercial areas.
Ambient conditions
Operating temperature
0
50
°C
Storage temperature
-25
70
°C
Humidity
(not condensing)
10
40
85
%H
rel
Degree of soiling
2
Connections
Supply 230 V AC
Screw terminals
SMI interface
Spring terminals
KNX bus system
Spring terminals
Connection terminals
Supply 230 V AC
max. 2.5 mm²
Stripping length
6.5 mm
Torque
0.5 - 0.6 Nm
SMI interface
max. 1.5 mm²
Stripping length
8 mm
KNX bus system
0.6 - 0.8 mm
∅
Stripping length
6 mm
Housing
Degree of protection
IP30
Safety class
II
Overvoltage category
III
Input/output
insulation voltage
4 kV AC / 1 min
Article number
KNX/SMI Actuator
REG-3TE 16K BT
4002 000 001 0
Becker-Antriebe GmbH
Friedrich-Ebert-Straße 2-4
35764 Sinn/Germany
60 mm
95 mm
90 mm
54 mm
3 MW
60 mm
Fig. 4
Dimensions
Summary of Contents for KNX/SMI Actuator REG-3TE 16K BT