Page 1: ... Actuator Important information for fitters certified electricians operators Please forward accordingly These instructions must be kept by the operator 4002 630 009 0 01 03 2022 Becker Antriebe GmbH Friedrich Ebert Straße 2 4 35764 Sinn Germany www becker antriebe com ...

Page 2: ...002 630 011 0 You can download the software manual and the product database for the actuator from www becker antriebe com downloads or from the ETS online catalogue Installation The device is intended for installation in a distribution cabinet The device is installed by clipping it onto a DIN rail TH 35 DIN 60715 Electrical connection An on site overload current protection device fuse and a discon...

Page 3: ...arameterised SMI bus not yet commis sioned or no motors in the internal motor list Maintenance There are no parts inside the device that require mainte nance Cleaning Clean the housing with a soft dry cloth Do not use deter gents cleaning agents solvents abrasive substances or steam cleaners Liability Failure to comply with the product information in these in structions and any use of the device o...

Page 4: ...C Conformity Available at www becker antriebe com ce This device meets the EMC directives for use in residen tial and commercial areas Ambient conditions Operating temperature 0 50 C Storage temperature 25 70 C Humidity not condensing 10 40 85 Hrel Degree of soiling 2 Connections Supply 230 V AC Screw terminals SMI interface Spring terminals KNX bus system Spring terminals Connection terminals Sup...

Page 5: ... BN BK GY GNYE M SMI I PE L N I Motor 1 Motor 2 Motor 15 Motor 16 5 1 5 mm2 All motor lines H05RR F 5 G 0 75 BK Example Connection of SMI motors Maximum of 16 motors Total power maximum 3600 VA for the power saving relay of the SMI drives Connection when using motor lines H05RR F 5 G 0 75 with two black wires I Black 1 between BL and GNYE I Black 2 between BN and GNYE X6 Auxiliary voltage connecti...