Technical data
Type
Control unit dimensions (W x H x D):
approx. 200 x 400 x 155 mm incl. mounting brackets
approx. 200 x 400 x 184 mm incl. mounting brackets and main switch
Assembly
Vertical
Supply voltage via L1, L2, L3, N, PE:
400 V 3~N PE ±10%, 50...60 Hz
Power consumption of the control unit:
max. 30 W when fitted to full capacity
Power output T1 / N (230 V):
corresponds to supply voltage, fused with 6.3A fuse
Power output
24 VDC (±10% at rated voltage 230 V) max. 500 mA
Inputs (FE 1 – FE 8):
typ. 24 VDC / <10mA +/- 20%
All inputs must be connected potential-free:
min. signal duration for input control commands: > 100 ms
Safety chain / EMERGENCY STOP
It is imperative that all inputs are connected potential-free
Contact load rating: 200 mA / 30 V DC
Safety inputs SE1 and SE2
For electric safety edges with 8.2 kΩ / 1.2 kΩ terminating resistance and for dynamic
optical systems 5.1 kOhm slack rope switch/wicket door switch
Secure functions
(EN ISO 13849-1:2008)
Safety edge:SE1, SE2
Category 2 / PL d
Optoelectronic safety edge
OSE: FE1
Category 2 / PL d
Light barrier with testing
Category 2 / PL d
Emergency Stop
Category 2 / PL d
Path limitation
Category 2 / PL c
Membrane keypad
Category 2 / PL d
Safety radio receiver
Category 2 / PL d
Relays Rel1 and Rel2
For inductive switching loads, suitable interference suppression measures should be
put in place
Change-over contact potential-free
3 A / 250 V AC; 3 A / 30 V DC
Relay Rel3
Potential-free normally open contact
0.5 A/24 VDC
Output power (motor)
Relay: P
max
: 2.0 kVA
Contactor: P
max
: 4.5 kVA
Temperature range
Operation:
-10...+40°C
Storage:
-20...+70°C
Humidity
Up to 95%, non-condensing
Vibration
Low-vibration installation, e.g., on a brick wall
Degree of protection
IP54 (optional: 65)
Weight
Approx. 3.5 kg
Attention
Contacts used once for power switching cannot switch any further small currents.
62