![Beck 990 Series Manual Download Page 8](http://html.mh-extra.com/html/beck/990-series/990-series_manual_2718166008.webp)
8 - 8
Func
2
lin
-
Analogue output is displayed (linear / square root)
lin / rAd
-
Set output signal to linear / square root
rAd
-
Save setting (
Display flashes for confirmation
)
CAL
2
0.52
-
k-factor is displayed
0.01
… 1.00
-
Set k-factor
CAL / rho
0.80
-
Save setting (
Display flashes for confirmation
)
1.00
-
Density rho of the medium is displayed
rho
0.80
… 1.50
-
Set rho
1.25
-
Save setting (
Display flashes for confirmation
)
HI
267
Pa
Maximum pressure (
peak value
) is displayed
Lo
0
Pa
Minimum pressure (
peak value
) is displayed
dISP
2
10
%
Brightness of LED is displayed
10
… 100
%
Set brightness
50
%
Save setting (
Display flashes for confirmation
)
=>
In programming mode always set to 100%, if a hardware
reset is performed, the brightness always goes to the set value
Uni
2
1
Pa
Pressure unit is displayed
1
… 3
Pa /
mbar /
inWC
Set pressure unit (LED 1
…2...3 on the front)
LED1 Pa; LED2 mbar; LED3 inWC
2
mbar
Save pressure unit (
Display flashes for confirmation
)
OP-h
48
h
Operating hours is displayed
Fir
F.2.01
Pa
Version of firmware is displayed
PArA
P. 21
Pa
Parameter number is displayed
PASS
3
32
-
Password is displayed
0
… 99
-
Set password
77
-
Save password (
Display flashes for confirmation
)
=> Active after hardware reset
End
2.00
mbar
Menu end / back to the pressure display
Note:
The table shows the maximum configuration. Availability of menu items depends on the ordered configuration
*
The main menu points are reached by turning
the rotary button
**
This function is only available from the Firmware F.2.02
1
Menu item can only be selected at 990M
- Option 1: Adjust the zero shift
- Option 2: Adjust the zero offset only in unpressurized condition
2
Functions are blocked - except if the password is "0" or "71 (Master password)"
3
Master password= 71 enables access to the instrument if the password is lost
8.930.276-1
990
manual german_english
8.930.
276
-1
Technische Änderungen vorbehalten. /
Technical data subject to change without prior notice.