background image

 

     

Page 3

Description and Operation

BEACONMEDÆS Anaesthetic Gas Scavenging (AGS) terminal 

units are designed to fully comply with BS6834:1987 and 

accept probes to the same standard, their installation fully 

satisfies the United Kingdom Health Technical 

Memorandum’s HTM2022 and HTM02-01. AGS terminal 

units are used as outlets to fixed pipeline installations to 

supply a maximum flow rate of 130 L/min. with a 1kPa 

pressure drop applied and make a connection point 

between a suitable receiver unit and disposal system 

pipeline. AGS terminal units may be wall mounted, for use 

with either surface or concealed pipeline installations or 

fitted inside a bed head trunking and pendant assemblies.

Each terminal unit is designed to be fully gas specific, with 

gas specific sub-components to prevent inadvertent incorrect 

assembly with Medical gas services. The BEACONMEDÆS 

AGS terminal units will only accept the correct service 

probe, thereby preventing inadvertent operator error. Gem 

10 terminal units are clearly identified in accordance with 

BS6834:1987 and are subject to comprehensive QA controls 

during manufacture with batch numbers allocated to the 

assemblies to provide traceability.

Operating Instructions

The probe is attached by pushing in fully home into the 

terminal unit and screwing the retaining nut loosely onto 

the second fix using hand pressure only. The probe pushes 

the valve plug of its seat and allows a flow of gas through the 

flow adjustable valve plug. This plug is specifically designed 

to provide an adjustable device allowing for fine tuning of 

the terminal unit to achieve the correct flow. 

Safety Information

WARNING

DO NOT USE OIL OR GREASE ON ANY NIST FOR ANY 

REASON! DOING SO COULD LEAD TO A FIRE OR EX-

PLOSION! 

Use only approved oxygen compatible lubricants, which can 

be purchased from BeaconMedæs if necessary.

Testing

All testing and commissioning should be completed in 

accordance with the installation contract.

Installation of Wall and Bed Head Mounted Units 

General requirements

Vertically mounted terminal units are installed in the 

location and the quantity detailed in the contract 

specification, however the following requirements should be 

met unless otherwise stated:-

Terminal units shall be located at a height of between 

900mm and 1400mm above finished floor level to the centre 

line of the terminal unit.

Multi-gas terminal unit installations when vertically 

mounted shall be spaced at 135 ± 2.5mm between centres.

The centre of a vertically mounted terminal unit shall be not 

less than 200mm from any possible obstruction on either 

side.

Wall mounted terminal units shall be housed in either 

individual or common (multi-gas) fascia plates.

Vertically mounted terminal units shall be mounted, when 

facing the units, in the following order, horizontally from left 

to right or vertically from top to bottom: -

O2, N2O, O2/N2O, Medical Air, Surgical Air, CO2, N2, VAC, 

AGS.

Installation procedure – surface and concealed

A single gas terminal unit required as a concealed 

installation requires a chase 95mm square to a depth of 

50mm including plaster depth and a chase suitable for the 

15mm downdrop pipe). Surface terminal units are installed 

separately and attach directly to the wall. In both cases care 

must be taken to ensure that each individual terminal unit 

is correctly aligned and square, and correct spacing between 

centres must be maintained. Multiple concealed terminal 

units are mounted on a multiple gas jig plate, which must 

be installed first. The procedure to install a BEACONMEDÆS 

AGS terminal unit 1st fix assembly is as follows: -

Single terminal unit (concealed). Chase. 

Identify correct location. Accurately chase wall 95mm square 

to a depth of 50mm including plaster depth and chase wall 

suitable for downdrop pipe. Ensure that chase depth enables 

terminal unit to be located squarely.

Single terminal unit (surface and concealed). 

Locate backplate. Offer terminal unit to wall, check 

location, alignment and correct spacing. Ensure that stub 

pipe aligns with downdrop pipe. Mark position of securing 

holes (4 - off provided, normally two are sufficient). In the 

event that the stub pipe needs shortening do this now using 

a wheel cutter.  Ensure that ends are square, free from burrs 

and re-round as necessary. Ensure that component is clean 

and blow through as necessary to remove any particles.

Distribution system. Purge. 

Using Medical quality air, purge downdrop pipe and 

associated distribution system to remove all particulate 

matter prior to fitting terminal unit.

Single terminal unit (surface and concealed). Fit. 

Drill wall and fit anchors. Locate backplate, align stub pipe 

with downdrop pipe, fit securing screws and tighten.

Multi-terminal units (concealed). Fit. 

Locate backplate on multiple gas jig plate securing studs (2 

- off). Ensure that stub pipe aligns with downdrop pipe. Fit 

Reviews: