Master Station Quick Start Guide 

B1M2, B1M4, B1M8 

 

The Beacon Master Station is a ready out of the box EVC system suitable for standalone 

applications up to 8 lines. It is very simple to install, requiring no set up or software, and is 

compatible with a range of outstations and the Assist Call range of emergency assistance 

alarms. 

 

This guide summarises applicable information from the full manual, which is 

available by scanning this QR code or visit espuk.com 

 

 

Figure 1 

1.

 

Mounting Information 

Master stations should be mounted in fire control rooms or next to the fire alarm panel at a 

mounting height of between 1.4 and 1.5m above finished floor level to the centre of the 

controls. Type A outstations (fire telephone) are generally fitted in fire-fighting lobbies and 

fire and rescues access points at 1.3 to 1.4m above (FFL). Type B outstations are used in 

disabled refuges at a mounting height of 0.9m to 1.2m (FFL). For Emergency assistance 

alarms refer to product manual. 

2.

 

Cable Information 

Fire telephone systems utilise Type A outstations and must use enhanced grade fire resistant 

cabling throughout for all wiring, including the mains supply to the master station. Max 

distance using 1mm or 1.5mm cable is 500m from outstation to master station. 
Disabled Refuge systems utilise Type B outstations, they are wired in standard or enhanced 

grade fire resistant cabling Refer to BS 5839-9:2021 for full details. 
Max distance using 1mm or 1.5mm cable is 500m from outstation to master station.  
Emergency assistance alarms (Assist Call) for dedicated circuits use 1mm 2 core flex for 

lengths of 500m from the master or security cable for shorter lengths from up to 50m for 2 

cores up to 200m if 4 cores are twisted together. If sharing with a Type B use the same 

grade of fire resistant cable.  