Beacon/Morris twin-floIII Installation Instructions Manual Download Page 7

STEAM CONDENSATE 
DIAGRAM

                               

           

 REPLACEMENT PARTS LIST

ACCESSORIES

7.

On a typical forced hot water system, connect return to inlet side of circulator and supply upstream of re-
motely operated valve. Unit may also be connected to mains of an existing loop system of suffi cient capacity. 
Operation will be infl uenced by the system circulator and associated controls.

Installation of a pump and line voltage thermostat will provide the unit with its own “zone” control.

With the addition of a circulator pump, hot water storage tanks may be used (where codes permit) as a supply 
source if proper precautions are taken, and if realitively low water temperatures can be tolerated. Be sure tank 
can supply additional load of the Twin-Flo and 120° F water. Supply is taken from top of tank, and returns at 
the cold water inlet with a check valve. Do not return to bottom drain tapping.

Operation from steam boiler water is entirely possible as long as supply and return connection is installed be-
low level of water line on a steam boiler. This installation requires an optional circulator pump and line voltage 
thermostat. Check local building codes.

Model

Description

Part No.

42

84

120

Quick-Connect Hose Kit

HK-10

x

x

x

Model

Description

Part No.

42

84

120

Motor-Fan Assembly

BMKR02020-001

x

BMKR02020-002

x

BMKR02020-003

x

Standard Aquastat Assembly (120° – 105°F)

BMKR02024-001

x

x

BMKR02024-002

x

Low Temp. Aquastat Assembly (110° – 95°F)

BMKR0204-L01

x

x

BMKR0204-L02

x

Heating Element

BMKR02017-001

x

BMKR02017-002

x

J37R52064

x

2 Speed Fan Switch

J11R02029-001

x

x

x

Outlet Grille w/ screws (Model K only) (Black)

BMKR08778-B42

x

BMKR08778-B84

x

BMKR08778-B12

x

Louvered Front Panel (Model W only)

BMWR02172-001

x

BMWR02172-002

x

x

Louvered Front Panel (Model F only)

BMFR02165-001

x

BMFR02165-002

x

x

Louvered Front Panel (Model FK only)

FKR02437-001

x

FKR02437-002

x

x

Summary of Contents for twin-floIII

Page 1: ...loor level and check piping and wiring locations The air outlet should be facing but not extending beyond the toe space riser at the opening The air outlet should also be located at the bottom portion...

Page 2: ...TWIN FLO III TYPE K42 FIGURE A 2 TWIN FLO III TYPE K84 FIGURE B TWIN FLO III TYPE K120 FIGURE C Dimensions shown in English and metric...

Page 3: ...mply connect it to the 115 V line The blower then starts after a short warm up and stops a few minutes after the circulator shuts off see diagram 1 Adding a line voltage type room thermostat will perm...

Page 4: ...his case it will collect on the rotor blades and air passage of the unit Regular cleaning with a vacuum cleaner tool is advised with fre quency determined by prevailing conditions Always make sure tha...

Page 5: ...em and create a pressure drop towards the supply tee forcing water up into the unit The arrow on the tee should point in the direction of water flow Figure 2 Figure 1 cutaway Figure 2 cutaway A ventur...

Page 6: ...ble solutions a Water is not hot enough Check system water temp If radiant system low temperature aquastat may be needed b Water not circulating fast enough Kickspace heaters must have at least 1GPM f...

Page 7: ...valve Do not return to bottom drain tapping Operation from steam boiler water is entirely possible as long as supply and return connection is installed be low level of water line on a steam boiler Thi...

Page 8: ...any workmanship of any installer of the Product This limited warranty is conditional upon a shipment to the Manufacturer of that part of the Product thought to be defective Goods can only be returned...