background image

SIZE:

DRAWN BY:

TITLE:  MC-25 w/ SARGENT EL PANIC
DEVICE & AUTOMATIC DOOR OPERATOR

A

100 ENTERPRISE DRIVE
PITTSBURGH, PA  15275
PHONE: (412) 249-4100
FAX:       (412) 249-4101
EMAIL:   www.beasensors.com

REV BY:

KJG

KJG

80.0018.02

SCALE:

DATE:

NONE

17 MAY 2005

PART NO:

SHEET
1 OF 1

COM

DOOR

CONTROL

ACT

RED COMMON
BLACK N/O

COM
N/O

24 V 

TRANSFORMER

SARGENT

POWER SUPPLY

120VAC

GND

* N.C. = CONTACT CLOSED

WHEN RELAY NOT POWERED

SARGENT

PANIC

DEVICE

+24VDC

-24VDC

RELAY

24VAC

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.
FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,
CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT
LEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE
DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE
AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Summary of Contents for 80.0011.02

Page 1: ... MC 25 RELAY 1 RELAY 2 RED COMMON COM N O BLACK RED GREEN WHITE POWER 24 VAC POWER 24 VAC N O COMMON AUTOMATIC DOOR CONTROL ACT DC ELECTRIC STRIKE BRIDGE RECTIFIER IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 1863 OR 1 8...

Page 2: ...MATIC FLUSH BOLTS 110 VAC brown orange jumpers on 1 2 4 5 dry input from N O ISO Relay MC 25 2 RELAY 1 RELAY 2 NO Com NC NO Com NC RELAY 2 NO Com NC RELAY 1 NO Com NC jumpers on 2 3 5 6 dry input from pushplate black red blue yellow grey grey brown orange blue yellow ACT COM SAf 24V coil ACT COM SAf TITLE DUAL MC 25 s Pair of doors w Electric Strike in the active leaf and automatic flush bolts in ...

Page 3: ...DOOR CONTROL 1 ISO24 RELAY MC25 1 WET CONTACTS ELECTRIC STRIKE MOTOR DOOR CONTROL 2 DOOR CONTROL 1 24VAC TRANSFORMER 110 VAC yellow gray gray orange brown DK 12 BODYGUARD COM SAFETY 24 VAC data 7 data 6 NC 5 NO 4 COM 3 PWR 2 PWR 1 ACTIVE ACTIVE COMMON red black COMMON red white white blue gray gray green brown orange green gray yellow blue orange brown black red 5 6 7 ACTIVE MOTOR 8 3 4 NONE 1 OF ...

Page 4: ...DGE RECTIFIER 24 V TRANSFORMER 115 VAC orange brown PUSH PLATE COMMON gray CARD READER COMMON N O OPTIONAL N O gray Common TITLE MC 25 WITH SAME POWER SUPPLY FOR MAGLOCK NOTES 1 JUMPERS JP1 JP2 ARE PLACED ON PINS 2 3 AND 5 6 FOR WET CONTACTS 2 DOOR POSITION SWITCH CONTACTS CLOSED WHEN DOOR IS CLOSED 3 TRANSFORMER AND BRIDGE RECTIFIER CURRENT RATING MUST BE SUFFICIENT TO SUPPORT MC 25 AND MAGLOCK 4...

Page 5: ... 0 1 2 1 1 1 3 3 3 3 2 4 4 3 4 5 5 6 67 8 8 85 5 9 4 6 6 6 3 6 6 9 5 5 9 6 5 14 3 4 1 1 2 1 7 00 A B 7 0 83 00 5 6 6 8 6 6 6 B 3 14 3 C 1 4 1 4 5 6 A3 4 A 1 0 0 D0 ...

Page 6: ...E MC 25 WITH SEPERATE POWER SUPPLY FOR MAGLOCK ENG G purple N C red COM RELAY2 RELAY1 Activation blue yellow DOOR CONTROL MAGLOCK BRIDGE RECTIFIER 24 V TRANSFORMER 115 VAC orange brown PUSH PLATE COMMON gray CARD READER COMMON N O OPTIONAL N O gray Common MC 25 JP1 JP2 3 2 1 6 5 4 EXTERNALPOWER SUPPLY We open up New Horizons PH 412 249 4100 FAX 412 249 4101 B E A Inc 100 Enterprise Drive Pittsburg...

Page 7: ...ANIC DEVICE 24VDC 24VDC RELAY 24VAC IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 1863 OR 1 800 407 4545 MID WEST 1 888 308 8843 WEST COAST 1 888 419 2564 DO NOT LEAVE ANY PROBLEM UNRESOLVED IF YOU MUST WAIT FOR THE FOLLO...

Page 8: ...OOR CONTROL ACT RED COMMON BLACK N O 24 V TRANSFORMER COM N O COM N O OPTIONAL BRIDGE RECTIFIER D C ELECTRIC STRIKE VOLTAGE FOR RELAY FROM EXISTING APT BUZZER OR FIRE ALARM SYSTEM IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866...

Page 9: ...LY MAGLOCK WHITE GREEN BLACK RED POWER 24 VAC POWER 24 VAC N O COMMON WHITE GREEN BLACK RED POWER 24 VAC POWER 24 VAC N O COMMON IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 1863 OR 1 800 407 4545 MID WEST 1 888 308 8843...

Page 10: ... DOOR CONTROL ACT RED COMMON BLACK N O 24 V TRANSFORMER COM N O COM N O OPTIONAL BRIDGE RECTIFIER D C ELECTRIC STRIKE IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 1863 OR 1 800 407 4545 MID WEST 1 888 308 8843 WEST COAST...

Page 11: ...00 DOOR CONTROL ACTIVATION com n o red black gray gray orange brown red blue yellow black 120 VAC DOOR 2 MOTOR blue yellow orange white RECTIFIER ISO 24VAC COIL DRY CONTACT MOTOR 2 DOOR 1 1 5sec DELAY 0 5sec DELAY ELECTRIC STRIKE gray gray MC25 1 WET CONTACT TITLE DOOR PROS WITH 2 MC 25 s orange brown 24 VAC ENG G 1 OF 1 02 JAN 04 80 0023 We open up New Horizons A JED 01 ...

Page 12: ...ED 24 V TRANSFORMER RELAY GRAY GRAY COM N O PUSH TO OPEN N C CONTACT CLOSED WHEN RELAY NOT POWERED N O 2 COMMON 3 POWER 1 ACTIVATE COMMON BRIDGE RECTIFIER D C ELECTRIC STRIKE IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 ...

Page 13: ... RED 24 V TRANSFORMER GRAY GRAY COM N O PUSH TO OPEN ACTIVATE COMMON BRIDGE RECTIFIER D C ELECTRIC STRIKE BLACK RED GREEN WHITE POWER 24 VAC POWER 24 VAC N O COMMON IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 1863 OR 1 ...

Page 14: ...RMER GRAY GRAY COM N O PUSH TO OPEN ACTIVATE COMMON BRIDGE RECTIFIER BLACK RED GREEN WHITE POWER 24 VAC POWER 24 VAC N O COMMON MAGLOCK COMMON N O OPTIONAL NIGHT MODE KEY SWITCH IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 8...

Page 15: ... CLOSED IF PANIC CURRENT LOAD IS GREATER THAN 500 mA AN AUXILLARY RELAY MUST BE USED PLEASE CONTACT BEA TECHNICAL SERVICES FOR MORE INFORMATION 24 V TRANSFORMER COM N O PUSH TO OPEN BLACK PURPLE RED GRAY GRAY ACTIVATE COMMON BRIDGE RECTIFIER BLACK PURPLE RED PANIC HARDWARE IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DUR...

Page 16: ...ACTIVATE COMMON BLACK PURPLE RED GRAY GRAY BLACK PURPLE RED GRAY GRAY COM N O PUSH TO OPEN COMMON N O OPTIONAL A C ELECTRIC STRIKE IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8AM 5PM FOR AFTER HOURS CALL EAST COAST 1 866 836 1863 OR 1 800 407 4545 MID WEST 1 888 308 88...

Page 17: ...CLOSED BLUE BLUE YELLOW GREEN RED YELLOW 24 V TRANSFORMER PURPLE RED BLACK GRAY GRAY PUSH TO OPEN PUSH TO OPEN GREEN OPERATOR MOTOR VOLTAGE ACTIVATION COMMON SAFETY DOOR CONTROL LEFT APPRCH SIDE SSCAN RIGHT APPRCH SIDE SSCAN IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM ...

Reviews: