background image

Step 1

Place the Live In wire into the left hand
position of the connector, the switched
Live Out wire into the second from
left position of the connector and neutral
into right hand position of connector.
(see diagram 1).

Step 2

Set the timing as per timing table  
(see diagram 3). The black square illustrates
where the dip switch should be situated.
For example: 
10min 1 = OFF, 2 = ON, 3 = OFF, 4 = OFF

Step 3

To adjust lux level (i.e. the ambient light
level at which you would like your lights to
be activated via the PIR timer) please  
refer to the lux level rotary adjuster 
diagram. Rotate the lux level adjustment 
clockwise to decrease the level of light 
required to turn the lights on and 
anticlockwise to increase the level of light 
required to turn the lights on. See diagram 
1 for position of lux level adjustment. 

Step 4

Re-apply mains supply. The blue locator 
ring will light up around the PIR button. 
Your light or appliance, will now be 
switched off. Please refer to operation 
section.

Step 5

Reduce lux level to sufficient level by
rotating clockwise towards (–) if required.
(–) represents 0 lux level.

Installation Notes

N.B. After installation the PIR will require
approximately 5 minutes to initialise.

Outdoor Installation

Outdoor Unit can only be used in conjunction
with the surface mount box supplied. 
Take the surface mount box and remove 
the knock out section. It is recommend the 
hole is cut with a 20mm hole saw for 
cleanest effect. If required and to ensure 
IP66 waterproof rating, please use a suitable 
M20 cable gland use appropriate sealing 
washers. Mount the surface mount box on a 
secure surface using the mounting pack 
supplied. Place screw cover seals over the 
mounting screws. It is essential that the 
correct IP 66 rated connections are made to 
keep the integrity of the IP rated back 
box maintained. Mount timer unit onto 
surface mount box using the four screws at 
all four corners  ensuring even connection 
with the seal-Place screw cover seals 
over left and right screw cavities. Clip on 
front fascia plate.

Flexible Cable

 

– It is always better to use 

cable glands with flexible cable, with the 
gland connected at the bottom, rather than 
through the top. Ensure sealing washers 
are used with all connections and all glands 
and connections are done up tightly with 
a spanner to ensure water tightness.

SWA Glands

 

– SWA glands can be used 

but must be IP rated. The IP rating for the 
SWA gland guarantees only the 
connections to the SWA cable. You will still 
need a nylon sealing washer to maintain 
the IP rating from the gland to the switch 
housing back box. As a general rule, 
nylon washers work best with this type of 
application. Rubber washers can deform 
when used with metal glands. Connections 
must be done up tightly with a spanner 
to ensure water tightness.

3

INSTRUCTION GUIDE

 

|

 

OUTDOOR ILLUMINATED PIR TIMER – 3 WIRE

2 mins            5 mins         10 mins        15 mins         20 mins         30 mins         40 mins          60 mins

Reviews: