4.3 DIP switches
4.2 Status Outputs (relay contacts)
4.4 Cable routing, strain relief
3.1 DIP switch setting according to sensor (safety edge, switch contact)
4
Receiver
3
Transmitter
1
ON
*
Transmission frequency
869.525 MHz
1
ON
868.15 MHz
*
= factory setting
Further instructions see separate transmitter manuals.
Determine the cable routing
Break out the corresponding part of the cover if necessary
Punch hole into the grommet
Thread cable
Fix cable with the clamp (
➔
strain relief)
Cable Ø: 3.1 – 5.2 mm
… or use holes
in the base plate
Break out …
Hint:
Power supply
Conductor cross section 0.25 – 0.75 mm
2
4.1 Wiring: Power supply and outputs with control
Control unit with
NC input
Control unit with
1.2 kOhm NC input
12–36V
AC/DC
Control unit with
8.2 kOhm input
Remove J1!
Example: RFGate 3.2.T
Sensor connection DIP switch
Sensor connection DIP switch
Note:
IN1 = active
IN2 = not used
Terminals
4–5
Terminals
3–6
No power supply
closed
open
System ready, sensor not pressed
8k2
closed
Sensor pressed
closed
open
Terminals
4–5
Terminals
3–6
Wicket door open (with RFGate 3.W.T)
closed
open
Broken cable between sensor and transmitter closed
open
Transmitter with empty batteries
closed
open