4.0 Site Requirements
12
4.5
Ventilation of Compartments
1. Where the appliance is installed in a cupboard
or compartment, no air vents are required.
NOTE: The ventilation label on the front of the
outer case MUST NOT BE REMOVED when
the appliance is installed in a compartment or
cupboard.
2. B.S. 5440 Part 2 Clause 4.2 refers to room
sealed appliances installed in compartments.
The Solo 2 PF will run sufficiently cool without
ventilation.
4.6
Gas Supply (Fig. 13)
1. The gas installation should be in accordance
with BS 6891.
2. The connection of the appliance is a RC
1
/
2
(
1
/
2
in BSPT internal) located at the rear of the gas
cock.
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes
of a smaller diameter than the appliance gas
connection.
4.7
Electrical Supply
External wiring must be correctly earthed,
polarized and in accordance with CURRENT
I.E.E. WIRING REGULATIONS.
The mains supply is 230V ~ 50Hz fused at 5A.
NOTE: The method of connection to the
electricity supply must facilitate complete
electrical isolation of the appliance.
Connection may be made via a fused double-
pole isolator with a contact separation of a least
3mm in all poles and serving the appliance and
system controls only.