Fault messages
Fault
Cause
Remedy
Pump is not
running although
the power supply
is switched on
Electrical fuse
defective
Check fuses
No voltage supply to
the pump
Resolve the interruption to
the power supply
Pump is noisy
Cavitation due to
insufficient suction
pressure
Increase the system supply
pressure within the
permissible range
Check the delivery head
setting and set it to a lower
height if necessary
Building does not
warm up
Thermal output of the
heating surfaces is
too low
Increase setpoint (see 5.3)
Set control mode to
Δp-c
Code
Fault
Cause
Remedy
E 04
Undervoltage
Power supply too low
on mains side
Check mains voltage
E 05
Overvoltage
Power supply too high
on mains side
Check mains voltage
E 07
Generator
operation
Water is flowing
through the pump
hydraulics but there is
no mains voltage to
the pump
Check mains voltage
E 10
Blocking
The rotor is blocked
Contact specialist
technician
E 11
Pump running
dry
Air in the pump
Check volume flow /
water pressure
E 21
Overload
Sluggish motor
Contact specialist
technician
E 23
Short-circuit
Motor current too high Contact specialist
technician
E 25
Contacting/
winding
Winding defective
Contact specialist
technician