7.0 Site Requirements
15
© Baxi Heating UK Ltd 2011
7.3
Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 Clause 4.2 refers to room sealed
appliances installed in compartments. The appliance will
run sufficiently cool without ventilation.
7.4
Gas Supply
1. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
2. The connection to the appliance is a 22mm copper
tail located at the rear of the gas service cock (Fig. 10).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a
smaller diameter than the boiler gas connection
(22mm).
7.5
Electrical Supply
1. External wiring must be correctly earthed, polarised
and in accordance with relevant regulations/rules. In GB
this is the current I.E.e. Wiring Regulations. In IE
reference should be made to the current edition of
ETCI rules.
2. The mains supply is 230V ~ 50Hz fused at 3A.
NOTE: The method of connection to the
electricity supply must facilitate complete electrical
isolation of the appliance.
Connection may be via a fused double-pole
isolator with a contact separation of at least 3mm
in all poles and servicing the boiler and system
controls only.
Fig. 10
Gas Service Cock