19
910.024.1 - EN (AUS)
INSTRUCTIONS PERTAINING TO THE INSTALLER
LUNA HT 1.1000
CONCENTRIC PIPE Ø 110/160
(C13 – C33 – C43)
TWIN PIPE Ø 110
(C13 – C33 – C43 – C53 – C83)
GAS
PARAMETERS
ΔP
MAX HEAT OUTPUT
MIN HEAT OUTPUT
IGNITION LOAD
H536-H613
(rpm)
H541-H610
(pwm%)
H612
(rpm)
H609
(pwm%)
H611
(rpm)
H608
(pwm%)
(Pa)
G20
6650
100
2050
12
3900
25
180
G31
6200
80
1950
11,5
3900
35
180
TABLE FUMES PRESSURE AVAILABLE
GAS
PIPES
LENGTH
L
(m)
PARAMETERS
ΔP
MAX HEAT OUTPUT
MIN HEAT OUTPUT
IGNITION LOAD
H536-H613
(rpm)
H541-H610
(pwm%)
H612
(rpm)
H609
(pwm%)
H611
(rpm)
H608
(pwm%)
(Pa)
G20
0 m ÷ 2 m
6400
100
1850
11
3100
20
140
2 m ÷ 6 m
6650
100
1950
11,5
3900
25
300
6 m ÷ 10 m
6900
100
2050
12
4300
30
400
G31
0 m ÷ 2 m
6000
80
1700
10,5
3100
20
140
2 m ÷ 6 m
6200
80
1850
11
3900
25
300
6 m ÷ 10 m
6400
80
1950
11,5
4300
30
400
GAS
PIPES
LENGTH
L1 + L2
(m)
PARAMETERS
ΔP
MAX HEAT OUTPUT
MIN HEAT OUTPUT
IGNITION LOAD
H536-H613
(rpm)
H541-H610
(pwm%)
H612
(rpm)
H609
(pwm%)
H611
(rpm)
H608
(pwm%)
(Pa)
G20
0 m ÷ 15 m
6400
100
1850
11
3100
20
140
15 m ÷ 27 m
6500
100
1950
11,5
4300
30
190
G31
0 m ÷ 15 m
6000
80
1700
10,5
3100
20
140
15 m ÷ 27 m
6100
80
1800
11
4300
30
190