BAXI LUNA 310 Fi troubleshooting guide

Page 1

Fault

Cause

Suggested Solutions

Boiler does not start

No power at the

 

Check 

120 Vac

 at power cord outlet.

no LED's lit.

boiler

 

Check if main 

3.15 amp

 boiler fuse has blown.

Boiler does not start

#14 LED not lit

 No signal from external control. Remove wires from thermostat connections

but #12 LED is lit.

(call for heat)

1&2 at terminal strip and jumper it. If boiler starts replace switching relay.

Boiler does not start

#13 LED not lit

 

Open DHW tap fully, has pin moved out from DHW differential assembly to

but #12 LED is lit.

(call for DHW)

close micro switch (green wires)?  

No

; DHW flow valve diaphragm damaged

replace. If diaphragm OK clean and lubricate DHW valve rod.  

Yes

; check 

continuity across DHW micro switch, replace if faulty.

Boiler does not start

Low water pressure

 

Re-pressurize heating system till pressure gauge reads between 

1-2 Bar

but #12 and #13 or

on gauge. Check for and repair leaks in heating system.

#14 LED's are lit.

Primary/DHW sensor

 Check DHW/ Primary temperature sensors for cold resistance of approx 

faulty.

11 K 

 (resistance reduces with increase in temp), replace if faulty.

Pump not operating

 

Check for 

120 V

 at pump, if no power and sensors OK, replace main PCB.

 

120 V

 at pump, but pump not turning. Release jammed pump by removing

vent cap on front of pump and turning shaft counter-clockwise. If pump will not
turn. Drain boiler, remove pump head release and clean pump cartridge.

Air in system

 

If pump is running but the flow switch has not closed, or is "bouncing" up

and down, purge air from the pump and heating system.

Flow switch faulty

 

If pump is running but flow switch has not closed; has pin moved out from

diverter valve to close micro switch?  

No

; flow switch diaphragm damaged,  

replace. If diaphragm Ok clean and lubricate flow switch rod.  

Yes

; check 

continuity across primary flow micro switch, replace if faulty.

Pump running, flow

Air switch not

 

Check air switch has not stuck in the open position. To check, remove room

switch closed fan

operating

sealed door on boiler and pull suction tube from fan venturi. Gently suck on

not running

the end of the sensing tube, you should hear the air switch operating. Re-
connect the sensing tube and retry  lighting boiler, (signal from PCB to fan on
start is via the NC terminals on the air switch). If air switch OK replace PCB.