21. PARAMETERS SETTING
To set the boiler parameters press the (
–
) and (
–
) buttons together for at least 6 seconds. When the function is
active, the letters “F01” will appear on the display, alternating with the value of the parameter shown.
Changing the parameters
r 1SFTTUIF
+/–
) buttons to scroll through the parameters;
r 1SFTTUIF
+/–
) buttons to change each parameter value;
r 1SFTTUIFCVUUPO
) to save changes, the display shows “MEM”;
r 1SFTTUIFCVUUPO
i
) to leave the function without saving, the display shows “
ESC
”;
Description of parameters
Factory settings
24 F
1. 24 F - 1. 14 F
24
1. 24 - 1. 14
F01
Type of boiler
10
= sealed chamber -
20
= atmospheric chamber
10
10
20
20
F02
Gas used
00
= NATURAL (METHANE) -
01
= LPG
00 o 01
F03
Hydraulic system
00
= instant appliance
03
= appliance with external storage boiler
04
= appliance for heating only
00
04
00
04
F04/ F05
Setting programmable relays 1 and 2 (See SERVICE
instructions)
00
= no associated function
00
F06
Maximum temperature setpoint setting (°C)
00
= 85°C -
01
= 45°C
00
F07
Configuration DHW priority input
F08
Max heating power
(0-100%)
100
F09
Max DHW power
(0-100%)
100
F10
Min heating power
(0-100%)
00
F11
Waiting time in heating before a new ignition
(00-10 minutes) - 00=10 seconds
03
F12
Diagnostics (See SERVICE Instructions)
--
F13-F14-F15
Factory setting
00