![Baxi ECOGEN 24/1.0 Installation & Servicing Instructions Manual Download Page 8](http://html1.mh-extra.com/html/baxi/ecogen-24-1-0/ecogen-24-1-0_installation-and-servicing-instructions-manual_2711788008.webp)
Fig. 3
Key
1
Supplementary Heat Exchanger 13 Engine Alternator
2
Burner Supplementary
14 PCB Control
3
Ignition Electrodes
15 Water Flow Sensor
4
Flame Sensing Electrodes
16 Safety Thermostats
5
Supplementary Gas Valve
17 Flow Temperature Sensor
6
Engine Burner
18 Condensate Trap
7
Engine Ignition Electrode
19 Return Temperature Sensor
8
Engine Flame Sensing Electrode 20 Fan
9
Engine Gas Valve
21 Spool Valve Motor
10
Gas Inlet
22 Spool Valve
11
Boiler Flow
23 Venturis
12
Boiler Return
24 Overtravel Switches
3.2 Frost Protection Mode
1. If the boiler return temperature falls below 7° C, then the boiler pump and heating circuit pump/valve are activated or opened. If the temperature rises above 8° C, the frost
protection function will be terminated. If the boiler return temperature falls below 3°C, the supplementary burner will be switched on until the return temperature reaches
25°C and the appliance frost protection is stopped.
2. If the supplementary burner is locked, the engine burner will be used. In this case, the return temperature limit to start the burner is increased from 3 to 10°C.
3. If an existing room thermostat is to be used then further protection for the system can be incorporated by using a wall mounted frost thermostat. In certain circumstances
it may be necessary to fit a pipe thermostat. If the THINK Controller is used as a room sensor then it will act as a room frost protection unit as well see
3.3 Pump/Diverter Valve Protection
1. The pump and valve kick is a protective function aimed at preventing the pumps and valves from seizing.
2. Every Friday at 3.00am, the pumps and valves connected directly to the boiler unit are switched on 30 seconds and off for 30 seconds, one by one.
3.4 Legionella
1. When a DHW cylinder is fitted with a temperature sensor an antilegionella function can be activated, so that at initial DHW charge and there after at regular intervals the
cylinder is heated to destroy any legionella bacteria, the cylinder temperature is raised to 65°C.
2. By default this function is not active. Customers have the choice to activate the function and set how often, or on what day, and at what time this function runs.
Customers should be informed that the temperature reached may be considerably higher than their normal requirements (See
paragraph j).
page 9
4.0 Technical Data
4.1 Ecogen 24/1.0 and Ecogen 24/1.0 LPG
Summary of Contents for ECOGEN 24/1.0
Page 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Page 70: ...page 70 16 2 Milligrid 24 way Connector...
Page 71: ...page 71 16 3 14 way Connector...
Page 72: ...page 72 16 4 Engine Circuit...
Page 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Page 74: ...page 74 16 6 External Connections External Wiring...
Page 85: ...page 87...
Page 86: ...page 88...
Page 87: ...page 89 Section P...
Page 88: ...page 90...
Page 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Page 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Page 92: ...page 97...