12.4 REPLACING THE ELECTRONIC BOARD
When replacing the electronic valve, perform the following operations:
•
disconnect the boiler from the mains power supply.
• remove the front panel of the boiler;
• replace the electronic board;
•
power the boiler;
• set parameters F03 and F12 as described in the SETTING PARAMETERS section according to the boiler model indicated on
the rating plate.
Electronically calibrate the gas valve as follows:
•
connect the positive pressure test point of a pressure gauge, possibly water-operated, to the gas valve pressure test point (Pb);
•
open the gas tap and switch the boiler to the Winter mode;
•
open a hot water tap that can provide a flow rate of at least 10 litres a minute or make sure there is maximum heat demand;
• press buttons
and
together for 10 seconds. Press
when "ON" appears on the display;
• press
when "INF" appears on the display. The modulator current percentage flashes on the display;
• press
when the pressure gauge measures an increase from 0.2 to 0.4 mbar with respect to the value indicated in the burner
pressure/injectors table (REDUCED POWER); the modulator current percentage appears on the display;
• press
when the pressure measured by the pressure gauge reaches the value indicated in the burner pressure/injectors
table (NOMINAL HEATING OUTPUT);
•
after calibration, "MEM" flashes on the display for 5 seconds.
If a pressure gauge is unavailable, the automatic gas valve calibration procedure can be performed as follows:
•
open the gas tap and switch the boiler to the Winter mode;
• keep the front panel of the boiler closed;
•
open a hot water tap that can provide a flow rate of at least 10 litres a minute or make sure there is maximum heat demand;
• press buttons
and
together for 10 seconds. Press
when "ON" appears on the display;
•
after calibration, "MEM" flashes on the display for 5 seconds.
If one of the following symbols: C01 – C02 – C03 – C04 – C05 appears after calibration, repeat the gas valve calibration
procedure.
Check the mechanical calibration of the gas valve pressure adjuster, as described in the GAS CONVERSION section, before
electronically calibrating the gas valve
13. VISUALISATION OF PARAMETERS ON THE DISPLAY ("INFO" FUNCTION)
Press
for at least 6 seconds to display information concerning boiler operation.
When the “INFO” function is enabled, the message “A00” alternating with the boiler delivery temperature, is shown on the
display:
CG_1808
Press buttons
to display the following information:
A00
: current heating delivery temperature (°C);
A01
: current DHW temperature (°C);
A02
: current external temperature (°C) (with external sensor connected);
A03
: current fumes temperature (°C);
A04
: instantaneous (%) value of the gas valve control signal;
A05
: power range (%) (MAX CH);
A06
: heating setpoint temperature (°C);
A07
: DHW temperature setpoint (°C);
A08
: last error that occurred in the boiler;
A09
: not used;
A10
: not used.
This function remains active for 3 minutes. It is possible to interrupt the “INFO” function in advance by pressing
or turning off
the power to the boiler.
Summary of Contents for Eco Compact
Page 23: ...45 7110102 03 1 06 13...
Page 25: ...47 r u 7110102 03 1 06 13 CSQ ISO 9001 ISO 14001 OHSAS 18001 A...
Page 27: ...49 r u 7110102 03 1 06 13 1 2 1 1 C...
Page 28: ...7110102 03 1 06 13 50 r u 2 3 B 1 1 5 C A A B C 4 5 G20 GPL G31 6 5 C 30 C C a...
Page 30: ...7110102 03 1 06 13 52 r u SECTION E 60 C 45 C F06 001 9 SECTION C G3 4 30 10 1 SECTION D...
Page 41: ...63 r u 7110102 03 1 06 13 16 2 3 2 0 5 3 5 30 E25 24 10 3 17 SECTION E Q H...
Page 45: ...67 7110102 03 1 06 13...
Page 58: ...7110102 03 1 06 13 214 S E C T I O N C 30...
Page 59: ...215 S E C T I O N C 7110102 03 1 06 13...
Page 60: ...7110102 03 1 06 13 216 S E C T I O N D...
Page 63: ...219 S E C T I O N F 7110102 03 1 06 13 CG_2518 M M2 A D C E B F G A ext...
Page 64: ...7110102 03 1 06 13 220 S E C T I O N F 2 1 D A C G H E F B...
Page 65: ...221 7110102 03 1 06 13...
Page 66: ...7110102 03 1 06 13 222...