9 Settings
Combi 2
53
9
Settings
9.1 Accessing the
settings
Fig.62 Step 2
To display/change the list of SERVICE settings, proceed as follows:
press the
F3
key, the
symbol on the menu bar starts to flash;
turn the
knob until you reach the
symbol to access user settings,
symbol to access installer settings, then
knob to enter code
0012
turn the
key to confirm;
To view/modify the list of settings, it is also possible to connect the
Bluetooth interface to the boiler via the connector
X10
. Then interface the
handset (SERVICE) to the boiler using the
SERVICE TOOL
software.
9.2 List of
parameters
Important
The factory settings for certain settings may differ based on the
market the product is destined for.
Tab.26
Table of parameters
Name
Description
Factory
value
Minimum
Maximum
Level
AP001
Operation of contact X15 (also see setting AP098)
1: Contact open —> Heating, domestic hot water and
antifreeze
disabled (error code H02.10)
2: Contact open —> Heating,
domestic hot water
disabled (error
code H02.09)
3: Contact open —> Heating, domestic hot water and
antifreeze
disabled (error code E02.13 with reset
request)
2
–
–
Installer
AP002
Manual heating request enabled based on
implementation of setting
AP026
0: Disabled
1: Enabled
0
–
–
Installer
AP006
Notification of low pressure in the heating installation
[bar]
0.8
0.6
3.0
Installer
AP009
Hours of burner ignition before the maintenance
notification with AP010=1
3000
0
51,000
Installer
AP010
Enables/disables maintenance notifications:
0: No notification
1: Customised notification (depending on settings
AP009 and AP011)
0
–
–
Installer
Danger
FOR LOW TEMPERATURE HEATING INSTALLATIONS
MODIFY SETTING CP000 ACCORDING TO THE MAXIMUM
FLOW TEMPERATURE.
turn until you reach the
press the key to confirm;
if accessing the installer menu, use
the and confirm by pressing the key
knob until you reach the desired setting, then press the
knob;
modify the value of the setting using
the press to confirm;
press to exit.