Electrical data
Instruction handbook Mains filters
BFN
Document No.: 5.09010.03
Baumüller Nürnberg GmbH
32
3.4
3.4.2
Filters for IT-systems
BFN 3-1-... -002
150
0250
0320
0400
0600
Max.
power supply
3 x 480 V
AC
+10 %, 50/60 Hz
Rated current
(at T
B
=
50 °C)
150 A
250 A
320 A
400 A
600 A
Peak current
(at T
B
= 50 °C)
4 x I
N
at switch-on
1,5 x I
N
for < 1 min / once per hour
Test voltage
Cable - Cable: 2150 V
DC
/ 2 s
Cable - Cabinet: 2700 V
DC
/ 2 s
Connection
Bolt M10
Rail with hole
11mm
PE: Bolt M12
Rail with hole
11mm
PE: Bolt M12
Rail with hole
11mm
PE: Bolt M12
Power loss (typical)
30 W
60 W
40 W
50 W
65 W
Protection class
IP 00
BFN 3-1-... -102
0320
0400
0600
1000
Max.
power supply
3 x 480 V
AC
+10 %, 50/60 Hz
Rated current
(at T
B
=
50 °C)
250 A
320 A
400 A
1000 A
Peak current
(at T
B
= 50 °C)
1,5 x I
N
for < 3 min per hour
or
2,5 x I
N
for 30 s per hour
Test voltage
Cable - Cable: 2280 V
DC
/ 2 s
Cable - Cabinet: 2690 V
DC
/ 2 s
Connection
Rail with hole
11mm
PE: Bolt M10
Rail with hole
14mm
PE: Bolt M12
Power loss (typical)
31 W
48 W
84 W
Protection class
IP 00