Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
79
3
ing externally supplied mono devices) the maximum DC link voltage
is import-
ant, only.
The parameter can be changed in the inhibited drive status, only.
175.6
Max. device DC link voltage
The parameter is used in the PU temperature model, only.
Maximally provided or expected DC link voltage in V.
Important for devices, which support the PU temperature model (see status PU tempera-
ture model
), only.
The parameter effects the value of the maximum continuous current of the device
, only.
There is no reduction of the output current at the default value of the parameter. This
means that the default value remains if there is no change of the required operating con-
ditions to be expected.
The maximum mains voltage
is important for the mains rectifier unit, the active
mains rectifier unit and internally supplied mono devices, only. For other devices (includ-
ing externally supplied mono devices) the maximum DC link voltage
>
175.6
<
is import-
ant, only.
The parameter can be changed in the inhibited drive status, only.
175.7
PU max. continuous current actual value
The parameter displays the instantaneous value of the maximum accepted continuous
current of the power unit.
Important for devices, which support the PU temperature model, only (see status PU tem-
perature model
).
The parameter
>
175.7
<
is generated from the PU's nominal current
, whereat the
correction factors are considered, which are described in chapter "Operating conditions"
of the operating manual of the device.
m
Correction factor of the device's control cabinet temperature (ambient temperature
or surface temperature). The required temperature can be entered in parameter
.
m
Correction factor of installation altitude. The required installation altitude can be en-
tered in parameter
m
Correction factor of voltage supply, PU mains voltage or PU DC link voltage. The re-
quired voltage can be entered in parameter
or
Furthermore the maximum accepted continuous current in dependence of the output fre-
quency
can be reduced, as described in chapter "Output frequency dependent
current derating" in the operating manual of the device.
If the current limit safety function of the overload monitoring PU temperature model has
responded, the maximum current of the drive
is limited to the max. PU instanta-
neous value of continuous current
>
175.7
<