Configuration
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
70
3.4
The value in this parameter is valid for the required operating requirements. See chapter
"Technical data" in the Instruction Handbook.
The currently valid power unit peak current dependent of the entered PWM frequency
There is no connection between the peak current (
>
129.85
<
to
>
129.88
<
) and the peak
current time
. The maximum permitted time for the peak current is specified in
chapter "Technical data" of the Instruction Handbook of the device.
129.92
Fan configuration
Factory setting of the existing fans in the device. During operation is checked if all the con-
figured fans are operating. In case a fan fails the error message 223 "Fan failure" ap-
pears.
In the additional identification "Info 1" can be seen which fans failed.
130.1
Heat sink temperature
Power Unit Heat Sink Temperature
130.2
Interior temperature
Internal temperature of the device.
130.3
DC link actual voltage
This parameter has the same meaning at the axis units as well as at the active mains rec-
tifier unit.
Actual value of the DC link voltage
130.8
Main supply voltage
Reserved
NOTE!
At the failure of one fan the device should be immediately repaired as a further oper-
ation can cause overheating and the permanent destruction of the device.