Controllers
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
492
3.7
3.7.5.3 Description of the Field Weakening parameters
142.1
Field weakening mode
m
Bit 2:
Bit
Meaning
0
Field weakening type:
0: "At the voltage limit": Field weakening via the field weakening factor
.
1: "Permanent field current": Isd set value (
) = Field current preset
value (
)
Other details see
1
Threshold speed of the controlled field weakening characteristic:
0: Motor nominal speed (
).
1: Speed threshold field weakening
2
From FW version 01.15:
Correction of the PWM voltage
in the over modulation range
(relevant to breakdown torque controller):
0: Not active
1: Active
See note to bit 2
15 ... 3
Reserved