Description of the Software Modules and Parameters
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
97
4
129.16
Peak current 2 kHz
129.17
Peak current 4 kHz
129.18
Peak current 8 kHz
129.19
Peak current 16 kHz
The maximum accepted current of the power unit at the corresponding PWM switching
frequency
From firmware version 01.10 onwards the parameter is applicable only if the lxt model for
the PU overload monitoring is used (see status PU temperature model
Bit 0).
The value in this parameter applies to the required operating conditions: See chapter
"Technical data" of the device's operating manual.
The valid PU peak current dependent of the entered PWM frequency
, is dis-
played in the parameter
The value of the peak current (
, or parameter
) corre-
sponds to the maximum current by which the device may be operated at peak current pro-
cessing time
corresponding to the specifications in chapter "Technical data" of
the device's operating manual.
129.20
Overcurrent threshold
Monitoring the maximum converter current
129.21
Max DC-link voltage
Maximum DC link voltage
129.22
Max peak current time
The maximum time period, within the converter may be operated at peak current
complying with the specifications in the chapter
"Technical data" of the device's operating manual.
If the PU overload monitoring model is operated by the temperature model (see status PU
temperature model
), this parameter is not important.