Performing the commissioning
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
32
2.7
The "Encoder 1 Configuration" window opens.
Figure 15:
ProDrive: Encoder 1 configuration
13
Enter data when using a sine-cosine encoder without a HIPERFACE
®
interface. With
a sine-cosine encoder with a HIPERFACE
®
interface, the data are transferred auto-
matically over the HIPERFACE
®
interface - do not alter the data.
m
Sine-cosine without HIPERFACE
®
e.g. Number of Pulses = 512
m
Sine-cosine without HIPERFACE
®
e.g. Revolutions = 1
14
Enter the overspeed limit manually in the parameter list in the diagnostic block
[FB:006]:
Parameter number 006.005 and 006.007: enter the value 115%,
Parameter number 006.006 and 006.008: enter the value -115%