Connection cross section
Connection
method
Torque
Load
capacity
Motor PE
BM5323
BM5325
BM5331
BM5332
BM5333
refer to motor cable
Cable lug
for M4
Min. 1.4 Nm
Max. 1.8 Nm
see
BM5326
BM5327
BM5328
BM5334
BM5335
refer to motor cable
Cable lug
for M5
Min. 2.2 Nm
Max. 3.0 Nm
BM537X
refer to motor cable
Cable lug
for M8
Min. 10 Nm
Max. 13 Nm
Connection
cross section
Connection
method
Load capacity
X200
(SELV/PELV)
24 V voltage supply
Max. 1.5 mm²
(2 wire 2 pin)
Plug connector,
spring-clamp con-
nection
Max.
2.0
A
plug connector, max. 16 A
Connection
cross section
Connection
method
Load capacity
X1
(SELV/PELV)
Control inputs
BM503X-
XX0X
Max. 1.5 mm²
Plug connector,
spring-clamp con-
nection
Max.
8.0
A
X2
(SELV/PELV)
DIO
Max. 1.0 mm²
Plug connector,
spring-clamp
connection
Max.
8.0
A
X206
(SELV/PELV)
Supply for motor
temperature and
brake
all other
devices
Max. 1.5 mm²
Plug connector,
spring-clamp
connection
Max.
4
A
BM537X
Max. 2,5 mm²
Max.
16
A
Electrical connections
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
168
7.14