Installation
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
137
7
7.14.2.1 X200 - 24V voltage supply
X200
(SELV/PELV)
Control voltage (U
DC
)
according to EN 61131-2:1994, table 7
+ 24 V -15 % / +20 %
Requirements to the control voltage / 24 V-supply
The control voltage must accord to PELV (EN 61800-5-1, chapter 3.21) and accordingly
to SELV (EN 61800-5-1, chapter 3.35).
At a control voltage of < 24 V the fan power is reduced. Therefore, it can be necessary,
to reduce the output current.
Max. conductor
cross-section
Termination system
Loading capacity
1,5 mm
2
(2-wire cabling, 2-pin)
Connector,
spring clamp termination
max.
2,0
A
Connector max. 20 A
1
+24V
2
M24V