4.3
P1364
This parameter defines an upper bound or limit for the integral gain (I) and therefore limits
the master frequency.
The formula is:
Integral upper bound = maximum output frequency
x
.
This parameter can limit the maximum output frequency.
P1365
To avoid amplification of measurement noise in the controller output, a derivative digital
filter is inserted. This filter helps to dampen oscillations.
P1366
This parameter defines the percentage of output frequency limit during the PID control.
The formula is:
Output frequency limit = maximum output frequency
This parameter will limit the maximum output frequency. An overall limit for the output fre-
quency can be set in
.
P1364
Obere Grenze Integralverstärkung
0 to 100 %
EE
Upper bound for integral control
100 %
STOP
BM_u_UpperBoundIntegralControl
1:1
-
P1365
Hauptfilter Verzögerungszeit
0.0 to 2.5 s
EE
Primary delay filter time
0.0 s
STOP
BM_u_PrimaryDelayFilterTime
10:1
-
P1366
Ausgangsfrequenz Grenze
0 to 110 %
EE
Output frequency limit
100 %
STOP
BM_u_OutputFrequencyLimit
1:1
-