Procedure of the commissioning
Instruction handbook
b maXX
(BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08
Baumüller Nürnberg GmbH
54
8.2
3
By clicking on the
g
-symbol, select the entry „Output D.1“ („D“
⇒
Analog IO module
in position D, „1“
⇒
output 1) from the drop-down list.
Figure 21:
Output selection
4
Enter in menu Analog output link 1:
m
Source parameter
: „1171“,
m
Offset
: „0 dig“,
m
Shift factor
: „0“,
m
Scaling factor
: „1638 Dig/V“.
The voltage at the output point D.1 (see pin-assignment,
page 39) can be measured now by using the suitable measuring instrument. If +10 V has
been applied at the input D.1, then there will also be an output voltage of +10 V at the
analog output.
5
Repeat the test for output 2
With that, testing of the
Analog-IO-Module
is complete.
NOTE!
If no voltage can be measured at the output 1 (see pin assignment
on page 39), even though the voltage is changed at the input 1, then either
the
Analog-IO-Module
or the controller/controller unit is defective.