www.baumer.com
CombiView
DFON display
There are 9 different display modes available
Digital
Analogue
Bar graph
Tank
small
analogue
horizontal
tank illustration
large
same w. bar graph
vertical
bottle illustration
same w. value
Electrical connection
Pin 1
+
4…20 mA (not connected)
Pin 2
-
4…20 mA (not connected)
Pin 3
Relay 1
Pin 4
Relay 1
Pin 5
Relay 2
Pin 6
Relay 2
Com 1
FlexProgrammer ① red
Com 2
FlexProgrammer ① black
The PFMx with DFON display is delivered with terminal 1 and 2 not connected. The DFON is powered and will have data direct
through a special ribbon cable (UnitCom). Via UnitCom the DFON and PFMx transmitter can be programmed together when con-
necting the FlexProgrammer to Com 1 and COM 2 on the back of the display.
Pin 3 and 5 can be jumpered together if common supply is used for the two relays, e.g. via a M12 5-pin connector. Two galvanic
separated relay outputs will require a 8-pin M12 connector if plug connection is required. If cable glands is used the terminals 4...6
is connected via the screw terminals.
Electrical connection
Operators instructions
CombiPress, type PFMx
UnitCom
Page 5 / 32
Electrical connection
M12, 5-wire
M12, 8-wire
1 + supply, 4...20 mA
1 n.c.
2 Common for relays
2 + supply, 4...20 mA
3 - supply, 4...20 mA
3 Relay 1
4 Relay 1
4 Relay 1
5 Relay 2
5 Relay 2
6 Relay 2
7 - supply, 4...20 mA
8 n.c.
Cable gland
Transmitter
-
- supply, 4...20 mA
+
+ supply, 4...20 mA
Com 1 Red clip (FlexProgrammer)
Com 2 Black clip (FlexProgrammer)
Display
1
n.c.
2
n.c.
3
Relay 1
4
Relay 1
5
Relay 2
6
Relay 2
Com 1 Red clip (FlexProgrammer)
Com 2 Black clip (FlexProgrammer)
English