background image

Page 12

For technical questions, please call 1-888-866-5797.

Item 57394 

        

SAFE
ty

Op
ERA
ti

O

n

M

A

int
En

A

nc
E

in

St

A

ll

Ati

O

n

troubleshooting

problem

possible causes

likely Solutions

Compressor does 

not start or restart

1.  Tank(s) already pressurized.
2.  Battery Pack not properly 

connected. 

 

3.  Battery Pack not properly charged. 

4.  Battery Pack burnt-out. 

5.  Compressor needs service.

1.  No problem.  Compressor will start when needed.
2.  Remove Battery Pack, make sure there are no 

obstructions, reinsert the Battery Pack according 

to its shape (it should only fit one way), and press 

firmly until the Battery Pack locks in place.

3.  Make sure Charger is connected and operating properly.  

Give enough time for Battery Pack to recharge properly.

4.  Dispose of old Battery Pack properly or recycle.  

Replace Battery Pack.

5.  Have unit inspected by a qualified technician.

Compressor builds 

pressure too slowly

1.  Battery Pack wearing out. 

2.  Working environment too cold.
3.  Safety valve leaking. 

 

4.  Loose fittings.

1.  Dispose of old Battery Pack properly or recycle.  

Replace Battery Pack.

2.  Move compressor to a warmer location.
3.  Listen for air leaking from valve.   

If leaking, replace with identical valve with same rating.   

DO nOt SEAl OR tAMpER WitH SAFEty VAlVE.

4.  Reduce air pressure, then check all fittings 

with a soap solution for air leaks and tighten 

as needed.  Do not overtighten.

Compressor not 

building enough 

air pressure

1.  Air filter needs cleaning/replacing. 

2.  Check Valve needs service.
3.  Compressor not large enough for 

job. 

4.  Loose fittings. 

 

5.  Hose or hose connections 

too narrow.

6.  High altitude reducing air output.

1.  Check air filter.   

Clean and/or replace as needed.

2.  Have technician clean or replace, as needed.
3.  Check if accessory SCFM is met by Compressor.  

If Compressor cannot supply enough 

air flow (SCFM), use a larger Compressor.

4.  Reduce air pressure, then check all fittings 

with a soap solution for air leaks and tighten 

as needed.  Do not overtighten.

5.  Replace with wider hose and/or hose connections. 

6.  Higher altitudes require compressors with greater output.

Overheating

1.  Air filter needs cleaning/replacing. 

2.  Unusually dusty environment.

1.  Check air filter.   

Clean and/or replace as needed.

2.  Clean and/or replace air filter more often or 

move unit to cleaner environment.

Compressor 

starts and stops 

excessively

1.  Loose fittings. 

 

2.  Compressor not large 

enough for job.

1.  Reduce air pressure, then check all fittings 

with a soap solution for air leaks and tighten 

as needed.  Do not overtighten.

2.  Check if accessory SCFM is met by Compressor.  

If Compressor cannot supply enough 

air flow (SCFM), use a larger Compressor.

Excessive noise

Loose fittings. 

Reduce air pressure, then check all fittings with a soap solution 

for air leaks and tighten as needed.  Do not overtighten.

Moisture in 

discharge air

Too much moisture in air.

Install inline air filter/dryer, and/or relocate 

to less humid environment.

Safety Valve “pops” Safety valve needs service.

Pull on the ring on the Safety Valve.  If it still pops, replace.

Air leaks from 

pump or fittings

Loose fittings.

Reduce air pressure, then check all fittings with a soap solution 

for air leaks and tighten as needed.  Do not overtighten.

Air leaks from tank

Defective or rusted tank.

Have tank replaced by a qualified technician.  

Drain moisture from tank daily to prevent future corrosion.

  Follow all safety precautions whenever diagnosing or servicing the compressor.   

Disconnect power supply before service.

Summary of Contents for 20191C-B

Page 1: ...and the receipt in a safe and dry place for future reference 20j When unpacking make sure that the product is intact and undamaged If any parts are missing or broken please call 1 888 866 5797 as soo...

Page 2: ...fety Warnings WARNING Read all safety warnings and instructions Failure to follow the warnings and instructions may result in electric shock fire and or serious injury Save all warnings and instructio...

Page 3: ...a hazardous situation 5 Service a Have your compressor serviced by a qualified repair person using only identical replacement parts This will ensure that the safety of the compressor is maintained Ai...

Page 4: ...g any adjustments changing accessories or storing power tool Such preventive safety measures reduce the risk of starting the power tool accidentally 3 Recharge only with the charger specified by the m...

Page 5: ...alified electrician if you are in doubt as to whether the outlet is properly grounded Do not modify the power cord plug provided with the charger Do not use the charger if the power cord or plug is da...

Page 6: ...BA Installation Read the ENTIRE IMPORTANT SAFETY INFORMATION section at the beginning of this manual including all text under subheadings therein before set up or use of this product TO PREVENT SERIOU...

Page 7: ...ildren or pets to prevent injury 2 Locate the Air Compressor on a flat level surface to ensure proper pump lubrication and to prevent damage to the unit Keep at least 12 of space around the unit to al...

Page 8: ...inflation may result in an explosion High Pressure Tires and Small Inflatables WARNING Wear ANSI approved eye protection during use WARNING TO PREVENT SERIOUS INJURY AND DEATH FROM EXPLOSION Do not ov...

Page 9: ...Draining Moisture from Air Tank on page 11 11 Remove Battery Pack s 12 Clean then store Air Compressor indoors out of children s reach Emergency Depressurization If it is necessary to quickly depress...

Page 10: ...en parts damaged electrical wiring and any other condition that may affect its safe operation 2 AFTER USE wipe external surfaces of Air Compressor with a clean cloth 3 WARNING TO PREVENT SERIOUS INJUR...

Page 11: ...2 Place a collection pan under Drain Valve 3 Turn Drain Valve to open it Tilt Compressor forward to drain 4 When all pressure and moisture are released close Drain Valve Air Filter Maintenance 1 Remov...

Page 12: ...ean and or replace as needed 2 Have technician clean or replace as needed 3 Check if accessory SCFM is met by Compressor If Compressor cannot supply enough air flow SCFM use a larger Compressor 4 Redu...

Page 13: ...UCT IN FACT THE MANUFACTURER AND OR DISTRIBUTOR EXPRESSLY STATES THAT ALL REPAIRS AND PARTS REPLACEMENTS SHOULD BE UNDERTAKEN BY CERTIFIED AND LICENSED TECHNICIANS AND NOT BY THE BUYER THE BUYER ASSUM...

Page 14: ...y 1 15 Elbow Joint 1 16 Nut M3 3 17 Handle Grip 1 18 Self Tapping Screw ST4x18 2 19 Screw ST3x8 4 20 Battery Guide Rail 2 21 Battery Guide Rail Cover 2 22 PCBA 2 23 Plug 2 24 Battery Guide Rail Rod 1...

Page 15: ...Page 15 For technical questions please call 1 888 866 5797 Item 57394 Safety Operation Maintenance Installation Assembly Diagram...

Page 16: ...amages so the above limitation of exclusion may not apply to you THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS T...

Reviews: