batterX LFP3500 Product Manual Download Page 5

 
 

batterx.io 

 

V20.1 

LFP3500 

2.

 

INTRODUCTION 

 
 
 
 
The batterX LFP3500 is a lithium iron phosphate battery in the form of a 3.5kWh module. This module acts as a 
reliable memory in a variety of applications. They contain their own integrated BMS, which monitors and 
manages battery voltages, currents and cell information. The BMS also constantly adjusts all cell voltages to 
each other, which further increases the service life of these modules. The LFP3500 is particularly suitable for 
applications with high performance, small installation space, limited load capacity and long service life. 
Multiple batteries can be connected in parallel to increase capacity and performance.  
 

 

 
 

CHARATERISTICS 

 
 

 

Cathode material is made of LiFePO4 with safety performance and long life. 

 

The  battery  management  system  (BMS)  has  protection  functions  such  as  overcharging,  overcurrent  and 
high/low temperature. 

 

The system can automatically manage the charge and discharge status, current and voltage of each cell. 

 

Flexible  configuration,  multiple  battery  modules  can  be  connected  in  parallel  to  increase  capacity  and 
performance. 

 

Adopted self-cooling mode quickly reduced the overall system noise. 

 

The module has a lower self-discharge, up to 6 months without charging, no memory effect, excellent low 
charge and low discharge performance. 

 

The operating temperature ranges from -5°C to 50°C, (charging 0~50°C; discharging -10~50°C) with excellent 
discharge performance and lifetime. 

 

Small  size  and  light  weight, standard 19-inch embedded  design module is convenient  for installation and 
maintenance. 

 

Summary of Contents for LFP3500

Page 1: ......

Page 2: ...roduction 3 3 Specifications 4 4 Device interface 5 5 Communication hub 9 6 Safe handling 10 Schematic diagram of the solution 10 Explanation of symbols 10 7 Troubleshooting 11 Problem identification...

Page 3: ...ot expose the battery module to flames aggressive chemicals water or vapours Do not paint the battery module Neither internal nor external parts Do not connect PV cables directly to the battery module...

Page 4: ...TY GEAR Use properly insulated tools to prevent accidental electric shock or short circuits It is recommended to wear the following protective equipment when handling the battery module Insulating glo...

Page 5: ...ISTICS Cathode material is made of LiFePO4 with safety performance and long life The battery management system BMS has protection functions such as overcharging overcurrent and high low temperature Th...

Page 6: ...3 5 Charging voltage VDC 52 5 53 5 Recommended charge discharge current A 37 Max charge discharge current A 74 Peak charge discharge current A 100A 15sec Communication RS232 RS485 CAN Configuration ma...

Page 7: ...us It lights continuously to indicate that the battery is under protection SOC LED s 6 green LEDs to indicate the current capacity of the battery see LED table Start button Keep button pressed for mor...

Page 8: ...ol baud rate 500K to read battery information R485 Communication RJ45 port follows the RS485 protocol baud rate 9600 or 115200 to read battery information Link Port 0 1 Communication RJ45 connector fo...

Page 9: ...on off Discharge off Output 2 on Charge on off Charge off Output 3 on System error off System normal Run LED green lights constantly when charging flashing when discharging ALARM LED red flashes on al...

Page 10: ...ging end Cell balance Charge overvoltage Intelligent charging model Discharge undervoltage Charge discharge current limit Charging Discharging Overcurrent Capacity retention calculate High low tempera...

Page 11: ...multiple battery groups to communicate with each other thus increasing the possible number of battery modules in an installation For communication again a RS485 Modbus is used which is connected betwe...

Page 12: ...batterx io 10 V20 1 LFP3500 6 SAFE HANDLING SCHEMATIC DIAGRAM OF THE SOLUTION EXPLANATION OF SYMBOLS...

Page 13: ...ion Check if the charge discharge current is okay If it is check the RS485 communication otherwise change the inverter settings c Overvoltage If the charging voltage is above 54V the battery protectio...

Page 14: ...FIRE NO WATER Only a dry powder fire extinguisher may be used if possible move the battery pack to a safe area before catching fire WET BATTERIES If the battery has become wet or fallen into water ke...