J99x Series BASO® Replacement Pilot Burners

© 2017 BASO Gas Products

3

Part No. BASO-INS-J99xREPLACEMENT, Rev. B

www.baso.com

Turn Down Test with Y99AB Test Kit

To perform the turn down test with the Y99AB Test
Kit:

1.

Disconnect the thermocouple lead from the
BASO power unit.

2.

Set the Y99AB test kit to use the 0-50 millivolts
scale.

3.

Connect the Y99AB test kit leads as shown in
Figure 2. Connect lead 44549-8 to the
thermocouple lead, and connect lead 44549-7 to
the thermocouple connection of the BASO
power unit (see Figure 2).

4.

Push and hold down the reset button of the
BASO power unit until it remains down.

5.

Reduce the pilot flame by turning the manual B
valve to the point where the open circuit reading on
the Y99AB is not more than 4 millivolts.

6.

Cycle the main burner On and Off at least
three times. The main burner must ignite each time
within 4 seconds.

If you cannot secure ignition of the main burner
when the millivoltage reading is 4 millivolts, the pilots
are located improperly with respect to the main
burner. Relocate the pilot and repeat Steps 5 and 6.

7.

Return the pilot to normal operation by turning the
manual B valve to the fully opened position and
reconnecting the thermocouple to the BASO power
unit.

Thermocouple

Lead

Reset

Button

Pilot Burner

Gas Line

Thermostat

44549-7

44549

-8

Red

Black

MILLIVOLTS

D.C.

PE NN-B ASO  CO NTROL S

0

10

20

30

40

50

100

300

500

700

900

MILLIAMPS

0-500

MILLIVOLTS

0-1000 0-50

ADJUST

MILLIVOLTS

MILLIAMPS

Power
Source

Y99AB

Manual B
Pilot Valve

BASO
Power Unit

Figure 2: Turn Down Test Using Y99AB Test Kit

Turn Down Test without Instruments

If you do not have the Y99AB Test Kit, perform the
turn down test using the following steps:

1.

Reduce the pilot flame by turning the manual
B valve to a point where the pilot flame does not
impinge on the thermocouple (see Figure 3).

This flame must

ignite the main burner.

Figure 3: Turn Down Test without Instruments