9469200997
1-3
DGC-2020ES
CEM-2020
CSA Certification
The CEM-2020 and CEM-2020H are Certificated under CSA report 1042505 (LR23131-138S) and
evaluated to the following standards through CSA:
•
CSA C22.2 No. 0
•
CSA C22.2 No. 14
CE Compliance
This product has been evaluated and complies with the relevant essential requirements set forth in the
following EC Directives and by the EU legislation:
•
Low Voltage Devices (LVD) - 2014/35/EU
•
Electromagnetic Compatibility (EMC) - 2014/30/EU
•
Hazardous Substances (ROHS2) -2011/65/EU
Harmonized Standards used for evaluation:
•
EN 50178 -
Electronic Equipment for use in Power Installations
•
EN 61000-6-4 -
Electromagnetic Compatibility (EMC), Generic Standards, Emission Standard for
Industrial Environments
•
EN 61000-6-2 -
Electromagnetic Compatibility (EMC), Generic Standards, Immunity for Industrial
Environments
•
EN 50581 –
Technical Documentation for the Assessment of Electrical and Electric Products with
Respect to the Restriction of Hazardous Substances (ROHS2)
NFPA Compliance
Designed to comply with NFPA Standard 110,
Standard for Emergency and Standby Power
.
EAC Mark (Eurasian Conformity)
•
TC RUUS.HO03.B.00742
Physical
Dimensions.............................................. See
Installation
later in this chapter.
Weight
CEM-2020 ............................................... 2.25 lb (1.02 kg)
CEM-2020H ............................................ 1.90 lb (0.86 kg)
Functional Description
Contact Inputs
The CEM-2020 provides 10 programmable contact inputs with the same functionality as the contact
inputs on the DGC-2020ES. The label text of each contact input is customizable.
Contact Outputs
CEM-2020
The CEM-2020 provides 24 programmable contact outputs with the same functionality as the contact
outputs on the DGC-2020ES. Outputs 5 through 16 can carry 1 A. Outputs 17 through 28 can carry 4 A.
The label text of each contact output is customizable.
CEM-2020H
The CEM-2020H provides 18 programmable contact outputs with the same functionality as the contact
outputs on the DGC-2020ES. Outputs 5 through 16 can carry 2 A. Outputs 17 through 22 can carry 10 A.
The label text of each contact output is customizable.
Summary of Contents for DGC-2020ES
Page 6: ...iv 9469200997 Revision History DGC 2020ES ...
Page 7: ...9469200997 v DGC 2020ES Contents Contents CEM 2020 1 1 Troubleshooting 2 1 ...
Page 8: ...vi 9469200997 Contents DGC 2020ES ...
Page 20: ...1 12 9469200997 CEM 2020 DGC 2020ES ...
Page 26: ...2 6 9469200997 Troubleshooting DGC 2020ES ...
Page 27: ......