9146600990 Rev M
BE1-25A General Information
1-9
Voltage Acceptance Option A2
BUS VOLTAGE UPPER LIMIT
Maximum threshold adjustable from 100 to 150 Vac.
CONTROL
BUS VOLTAGE LOWER LIMIT
Minimum threshold adjustable from 80 to 120 Vac.
CONTROL
VOLTAGE DIFFERENCE CONTROL
Minimum threshold adjustable from 1 to 10 Vac of generator
voltage. (Generator voltage minus bus voltage)
Weight
8 oz (226.8 kg)
Frequency Matching Option F5
CORRECTION PULSE WIDTH
Adjustable from 0 to 99.9 seconds.
CONTROL
CORRECTION PULSE INTERVAL
Adjustable from 0 to 99.9 seconds.
CONTROL
Weight
6.6 oz (186.0 g)
Voltage Matching Option V1
Weight
5 oz (140.6)
Voltage Matching Option V2
CORRECTION PULSE WIDTH
Adjustable from 0.1 to 5.0 seconds.
CONTROL
CORRECTION PULSE
Adjustable from 0.2 to 10.0 seconds.
INTERVAL CONTROL
Weight
7.0 oz (200.0 g)
Voltage Matching Option V3
CORRECTION PULSE WIDTH
Adjustable from 0.1 to 5.0 seconds.
CONTROL
CORRECTION PULSE
Adjustable from 0.2 to 10.0 seconds.
INTERVAL CONTROL
Weight
8.5 oz (240.4 g)
Dead Bus Option D1
VOLTS CONTROL
Adjustable from 10.0 to 40.0 Vac.
Weight
6.6 oz (186.0 g)