BE1-25/79TR Functional Description
3-3
MODES OF OPERATION
BE1-25/79TR Sync-Check Reclosing Relays have two primary modes of operation. They are the status
mode and settings mode. These modes are selected by momentarily pushing the front panel Settings Select
Up/Settings Select Down or the Reset switches.
Settings Mode
To program a setting or a parameter, select the settings mode by momentarily pushing the Settings Select
switches (either up or down). The front panel CE LED will flash to indicate the settings mode has been
entered. The CE LED continues to flash while in the settings mode. All reclose and voltage monitor
functions are disabled except for some of the active function LED's. The LED's (LL, LB, DL, and DB)
indicate existing voltage conditions.
To select a setting or parameter, momentarily push (either up or down) the front panel Settings Select
switches. Each time the switch is operated, another parameter is selected as the display scrolls through the
available settable parameters. These parameters are as follows.
Front Panel Display
Description
Range
Address
Remote address for future use
1-254
K-BAUD
Communication Baud Rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6,
MASTER TD
Master Time Delay
1-999 seconds
RST1 TD
Reset 1 Time Delay
1-999 seconds
RST2 TD
Reset 2 Time Delay
1-999 seconds
HSR TD
High Speed Reclose Time Delay
1-999 cycles
LT1 TD
Line Test 1 Time Delay
1-999 seconds
LT2 TD
Line Test 2 Time Delay
1-999 seconds
RP1 TD
Restore Power 1 Time Delay
1-999 seconds
RP2 TD
Restore Power 2 Time Delay
1-999 seconds
PAR TD
Parallel Time Delay
1-999 seconds
SYNC TD
Sync Time Delay
1-999 cycles
PF TD
Power Fail Time Delay
1-99 seconds
LO TD
Lockout Time Delay
1-999 seconds
DEAD BUS
Dead Bus Voltage condition
10-135 volts
DEAD LINE
Dead Line Voltage condition
10-135 volts
LIVE BUS
Live Bus Voltage condition
10-135 volts
LIVE LINE
Live Line Voltage condition
10-135 volts
PHASE W
Phase Window
1-180 degrees
DELTA V
Delta Voltage Window
1-135 volts
FSLIP W
Slip Frequency Window
0.05-1.00 hertz
CLOSE TD
Close Output Time Delay
1-999 seconds
HSR-SYNC
High Speed Reclose with Sync-Check
YES-NO
START52B
Start Master Timer with only 52b
YES-NO
BKR RECG
52b Contact Sensing Input Recognition Time
2-50 (x4 msec)
LOP TD
Loss of potential Time Delay
0-999 (x10 msec)
TST MODE
Test mode Entry
Yes-No
YEAR
Year clock setting
00-99 years
MONTH
Month clock setting
01-12 months
Summary of Contents for BE1-25/79TR
Page 1: ...05647 6 10 07 14 19 241 5 0 4 15 0 4 64 Publication 9 2787 00 990 Revision B 07 95...
Page 27: ...BE1 25 79TR Controls and Indicators 2 7 Figure 2 7 Front Panel Vertical Mount Relay...
Page 29: ...BE1 25 79TR Functional Description 3 2 Figure 3 1 Functional Block Diagram...
Page 60: ...BE1 25 79TR Installation 4 8 Figure 4 9 RS 232 Interconnection Diagram For IBM Type Computers...
Page 63: ...BE1 25 79TR Testing 5 2 REAR VIEW FRONT VIEW Figure 5 1 BE1 25 79TR Test Simulator...
Page 64: ...BE1 25 79TR Testing 5 3 Figure 5 2 BE1 25 79TR Test Simulator Schematic Diagram Sheet 1 of 2...
Page 65: ...BE1 25 79TR Testing 5 4 Figure 5 3 BE1 25 79TR Test Simulator Schematic Diagram Sheet 2 of 2...
Page 66: ...BE1 25 79TR Testing 5 5 Figure 5 4 Test Setup Diagram...