1-10
BE1-24 General Information
Push-To-Energize-Output
Accessible with a thin non-conducting rod through the front panel,
Pushbuttons
push-to-energize pushbuttons are available to energize each output
relay for testing the external control/protective system wiring.
Shock
In standard tests, the relay has withstood 15 g in each of three
mutually perpendicular axes without structural damage or
degradation of performance.
Vibration
In standard tests, the relay has withstood 2 g in each of three
mutually perpendicular axes swept over the range of 10 to 500
hertz for a total of six sweeps, 15 minutes each sweep, without
structural damage or degradation of performance.
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one minute
dielectric (high potential) tests as follows:
All circuits to ground:
2121 Vdc
Input to output circuits:
1500 Vac or 2121 Vdc
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989,
Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay System,
and IEC 255-5,
Impulse Test and Dielectric Test.
Impulse Test
Qualified to IEC 255-5.
Radio Frequency
Maintains proper operation when tested in accordance with IEEE
Interference (RFI)
C37.90.2-1987
Trial-Use Standard Withstand Capability of Relay
Systems to Radiated Electromagnetic Interference from
Transceivers.
UL Recognition
UL Recognition per Standard 508, UL File No. E97033. Note:
Output contacts are not UL Recognized for voltages greater than
250 volts.
Temperature
Operating
-40
(
C (-40
(
F) to +70
(
C (+158
(
F)
Storage
-65
(
C (-85
(
F) to +100
(
C (+212
(
F)
Weight
17.3 pounds maximum
Case Size
All relays are supplied in a M1 double-ended case.
Summary of Contents for BE1-24
Page 9: ...1 4 BE1 24 General Information Figure 1 1 Inverse Square vs Two Step...
Page 10: ...BE1 24 General Information 1 5 Figure 1 2 Protection Characteristics of the BE1 24...
Page 12: ...BE1 24 General Information 1 7 Figure 1 3 Style Number Identification Chart...
Page 16: ...BE1 24 General Information 1 11 Figure 1 4 Inverse Square Characteristic Curves...
Page 19: ...2 2 BE1 24 Human Machine Interface Figure 2 1 Location of Controls and Indicators...
Page 27: ...4 2 BE1 24 Installation Figure 4 1 M1 Case Outline Dimensions Front View...
Page 30: ...BE1 24 Installation 4 5 Figure 4 4 M1 Case Double Ended Panel Drilling Diagram Rear View...
Page 31: ...4 6 BE1 24 Installation Figure 4 5 M1 Case Panel Drilling Diagram...
Page 32: ...BE1 24 Installation 4 7 Figure 4 6 M1 Case Projection Mounting Outline Dimensions Rear View...
Page 34: ...BE1 24 Installation 4 9 Figure 4 7 Typical Internal Connections...