66
9424200994 Rev U
Auxiliary Undervoltage (27X) Protection
BE1-11
g
Trip
The Trip output becomes true if an undervoltage pickup condition persists for the duration of the element
Time Delay setting or calculated inverse time. In BESTlogic
Plus
, the Trip output can be connected to
other logic elements and to a physical relay output to annunciate the condition and to initiate corrective
action. If a target is enabled for the element, the BE1-11
g
will record a target when the Trip output
becomes true. See the
Fault Reporting
chapter for more information about target reporting.
Voltage Inhibit
The Voltage Inhibit setting impedes auxiliary undervoltage element operation during undervoltage
conditions that may occur during equipment startup. This setting is expressed in primary or secondary
voltage depending on the Settings Display Mode selected on the General Settings/Display Units settings
screen in BESTCOMS
Plus.
Its unit of measure depends upon the auxiliary VT connection setting and 27X element mode selected.
For AB, BC, and CA sensing connections in Vx Fundamental or Vx Third Harmonic mode, the inhibit level
is expressed in Vpp. For AN, BN, CN, or Ground sensing connections in Vx Fundamental or Vx Third
Harmonic mode, the inhibit level is expressed in Vpn. The inhibit level is always expressed in Vpn for V1,
V2, and 3V0 modes of the 27X element.
Element Blocking
Fuse Loss
The fuse loss (60FL) element of the BE1-11
g
can be used to block 27X protection when fuse loss or loss
of potential is detected in a three-phase system.
If the 60FL element trip logic is true and Block Phase/V1 is enabled, the 27X function will be blocked
when configured for V1 mode. If Block V2 is enabled, the 27X function will be blocked when configured
for V2 mode. If Block 3V0 is enabled, the 27X function will be blocked when configured for 3V0 mode.
See the
Fuse Loss (60FL)
chapter for more information on the 60FL function.
Protective elements blocked by 60FL should be set so that trip times are 60 milliseconds or greater to
assure proper coordination of blocking.
Block Logic Input
The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. Connect the
element Block input to the desired logic in BESTlogic
Plus
. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.
Logic Connections
Auxiliary undervoltage element logic connections are made on the BESTlogic
Plus
screen in
BESTCOMS
Plus
. The auxiliary undervoltage element logic block is illustrated in Figure 48. Logic inputs
and outputs are summarized in Table 19.
Figure 48. Auxiliary Undervoltage Element Logic Block
Table 19. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 27X function when true
Trip
Output
True when the 27X element is in a trip condition
Summary of Contents for BE1-11g
Page 2: ......
Page 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Page 22: ...10 9424200994 Rev U Introduction BE1 11g...
Page 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Page 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Page 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Page 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Page 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Page 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Page 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Page 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Page 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Page 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Page 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Page 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Page 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Page 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Page 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Page 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Page 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Page 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Page 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Page 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Page 236: ...224 9424200994 Rev U Alarms BE1 11g...
Page 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Page 248: ...236 9424200994 Rev U Demands BE1 11g...
Page 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Page 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Page 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Page 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Page 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Page 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Page 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Page 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Page 290: ...278 9424200994 Rev U Mounting BE1 11g...
Page 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Page 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Page 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Page 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Page 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Page 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Page 374: ...362 9424200994 Rev U Device Information BE1 11g...
Page 392: ...380 9424200994 Rev U Configuration BE1 11g...
Page 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Page 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Page 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Page 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Page 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Page 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Page 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Page 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Page 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Page 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Page 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Page 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Page 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Page 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Page 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Page 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Page 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Page 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Page 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Page 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Page 705: ......