background image

not sufficiently sensitive to the ground current
level.

The 51V voltage-controlled or voltage-restrained
time overcurrent relay in Fig. 30 is shown on the
CT on the high voltage/system side of the
generator. This allows the relay to see system
contributions to a generator fault. It provides
back-up for the differential relay (87G) and for
external relays and breakers. Since it is monitor-
ing CTs on the system side of the generator, it
will not provide any back-up coverage prior to
having the unit on line. If there is no external
source, no 87G, or if it is desired that the 51V
provide generator protection while the breaker is
open, connect the 51V to the neutral-side CTs.

Fig. 30 shows three relays sharing the same CTs
with a differential relay. This is practical with
solid state and numeric relays, because their low
burden will not significantly degrade the quality of
differential relay protection. The common CT is
not a likely point of failure of all connected
relaying. A CT wiring error or CT short is unlikely
to disable both the 87G and 51V relays. Rather,
a shorted CT or defective connection will unbal-
ance the differential circuit and cause the 87G to
trip. Independent CTs could be used to provide
improved back-up protection, although this
seems to be a minimal advantage here. How-
ever, a separate CT is used for the 51N relay
that provides protection for the most likely type
of fault.

The reverse power relay (32) in Fig. 30 protects
the prime mover against forces from a motored
generator and could provide important protection
for the external system if the motoring power
significantly reduces voltage or overloads equip-
ment. Likewise, the loss-of-field relay (40) has
dual protection benefits—against rotor overheat-
ing and against depressed system voltage due to
excessive generator reactive absorption. Ther-
mal relay (49) protects against stator overheating
due to protracted heavy reactive power demands
and loss of generator cooling. Even if the
excitation system is equipped with a maximum
excitation limiter, a failure of the voltage regula-
tor or a faulty manual control could cause
excessive reactive power output. Frequency
relaying (81O/U) protects the generator from off
nominal frequency operation and senses genera-

tor islanding. The under and overvoltage function
(27/59) detects excitation system problems and
some protracted fault conditions.

Fig. 31 shows minimum basic protection for a
medium impedance grounded generator. It differs
from Fig. 30 only in the use of a ground differen-
tial relay (87N, part of CDS220 or BE1-67N). This
protection provides faster clearing of ground
faults where the grounding impedance is too high
to sense ground faults with the phase differential
relay (87G). The relay compares ground current
seen at the generator high voltage terminals to
ground current at the generator neutral. The 51N
relay provides backup for the ground differential
(87N) and for external faults, using the current
polarizing mode. The polarizing winding mea-
sures the neutral current.

FIGURE 31. SUGGESTED MINIMUM PROTECTION
EXAMPLE (MEDIUM-IMPEDANCE GROUNDED).

Fig. 32 shows minimum basic protection for a
high impedance grounded generator. It differs
from Fig. 30 only in the ground relay protection
and the method of grounding. The voltage units
59N/27-3N provide the only ground protection,
since the ground fault current is too small for
phase differential relay (87G) operation. The 59N
relay will not be selective if other generators are
in parallel, since all the 59N relays will see a
ground fault and nominally operate at the same
time. If three Phase-Ground Y-Y VTs were
applied in Fig. 32, the 27 and 59 could provide
additional ground fault protection, and an addi-
tional generator terminal 59N ground shift relay
could be applied.

17

Summary of Contents for BE1-1051

Page 1: ...GeneratorProtection ApplicationGuide...

Page 2: ...ign of protective relaying systems He worked for Consolidated Edison Company for ten years as a System Engineer He has served as a private consultant since 1982 Updates and additions performed by vari...

Page 3: ...it is rather expected that a 500kW 480V standby reciprocating engine will have less protection than a 400MW base load steam turbine unit One possible common dividing point is that the extra CTs neede...

Page 4: ...ral VFG in Fig 1 Assuming an impedancegroundedgeneratorwhere Z0 SOURCE and ZN ZWINDING the current level is directly proportional to the distance of the point from the generator neutral Fig 1 a so a f...

Page 5: ...rcuit or setting the relay fairly insensitively FIGURE 2 GROUND FAULT RELAYING GENERATOR LOW IMPEDANCE GROUNDING The neutral CT should be selected to produce a secondary current of at least 5A for a s...

Page 6: ...gh rejection of fundamental frequency voltage FIGURE 6 GROUND FAULT NEAR GENERATOR NEUTRAL REDUCES THIRD HARMONIC VOLTAGE IN GENERATOR NEUTRAL DROPPING OUT 27 3N The 27 3N performs a valuable monitori...

Page 7: ...ult as seen by the generator neutral shift sensing relay 59N leading to a generator trip Alternatively assume that the VT corner e g phase A has been grounded If phase B or C fault to ground the fault...

Page 8: ...2 100 5 from the neutral When feeder cables are connected to the gen erator bus the additional capacitance dictates a much lower level of grounding resistance than achieved with a unit connected case...

Page 9: ...hout pre loading For example assuming a pre fault 1pu rated load at 30 degree lag at one second the 3 phase fault value would be 2 4 times rated rather than 1 75 timesrated 1 30 1 75 90 2 4 69 Under t...

Page 10: ...edapproach inhibits operation until the voltage drops below a preset voltage It should be set to function below about 80 of rated voltage with a current pickup of about 50 of generator rated Since the...

Page 11: ...imes tap CDS220 or 0 4A 87G is representa tive of a recommended setting for a moderate mismatch in CT quality and burden Fig 13 also shows 51V relays to back up the 87G and external relays and breaker...

Page 12: ...nchroniz ing when the generator is initially slower than the system Since motoring can occur during a large reactive power flow the real power component needs to be measured at low power factors The B...

Page 13: ...y a mho circle centered about the X axis offset from the R axis by X d 2 Two zones sometimes are used a high speed zone and a time delayed zone FIG 19 LOSS OF EXCITATION USING IMPEDANCE RELAY With com...

Page 14: ...r during a fault To prevent a 60FL from being declared during loss of station power it may be necessary to allow a 3 phase 60F to be declared only when some low level of load current exists FIGURE 22...

Page 15: ...ach set point may be set to recognize either over frequency or underfrequency Multiple frequency set points are available in the BE1 81O U BE1 GPS100 BE1 951 and BE1 1051 Another common need for frequ...

Page 16: ...ld be employed where protection independent of the plant is desired In this case the 67 relays would be placed in the switchyard rather than in the control room While directional overcurrent relay 67...

Page 17: ...reaker depending on the type of fault that is detected For instance if the generator is protected by a 51V and an 87G and only the 51V trips it may be assumed that the fault is external to the generat...

Page 18: ...EXAMPLE OF BARE MINIMUM PROTECTION LOW IMPEDANCE GROUNDING Fig 30 shows the suggested minimum protection with low resistance grounding It includes differential protection which provides fast selectiv...

Page 19: ...ssive generator reactive absorption Ther mal relay 49 protects against stator overheating due to protracted heavy reactive power demands and loss of generator cooling Even if the excitation system is...

Page 20: ...voltage balancerelay 60 field ground relay 64F frequency relay 81 and the 27 50 62 relay combination for inadvertent energization protection Relay 51GN provides a second means of detecting stator gro...

Page 21: ...ures 34 through 37 show the BE1 GPS100 and BE1 CDS220 applied to generator protection Due to logic complexity full details are not shown Details of these applica tions may be found in the respective i...

Page 22: ...20 FIGURE 35 BE1 GPS100 APPLIED TO HIGH IMPEDANCE GROUNDED GENERATOR HI_Z_GND PREPROGRAMMED LOGIC SEE INSTRUCTION MANUAL FOR LOGIC DETAILS...

Page 23: ...FIGURE 36 BE1 CDS220 APPLIED TO GENERATOR FOR 87 PHASE 87 NEUTRAL AND 51 PHASE NEUTRAL GROUND AND NEGATIVE SEQUENCE 21...

Page 24: ...s typical settings for use as a starting point in the setting determi nation procedure The proper settings are heavily influenced by the specifics of each application Typical settings are also used as...

Page 25: ...urrent 49 20 StatorTemperature RTD Lower 95 C upper 105 C 50 87 12 Differentialviaflux PU 10 INOM or less if 1A relay may be used summationCTs 50 27 IE 24 InadvertentEnergization 50 0 5A 10 INOM Overc...

Page 26: ...75 100 INOM GEN Definite Time 0 1 0 25 sec InadvertentEnergization Inst 200 INOM GEN 81 21 Over underfrequency Generator protection 57 62Hz 0 5s Island detection 59 61Hz 0 1s 87G 13 GeneratorPhase BE1...

Page 27: ...9 59 X X X X X X 59N 27 3N 59N 59P 4 4 4 60FL 60 X X X 67IE 67 X X 81 81O U 81O U X X X X X 87G 87G X 87N 67N 87UD 87T X 1 50 51G Indicates a relay that monitors a ground CT source 2 50 51N Indicates...

Page 28: ...54 2341 Fax 1 618 654 2351 BaslerElectricInternational P A E Les Pins 67319 Wasselonne Cedex FRANCE Phone 33 3 88 87 1010 Fax 33 3 88 87 0808 If you have any questions or need additionalinformation pl...

Reviews: