2-1
!"#$%&'()
!"#$%"&'()#*(+#*+!)$"%'
GENERAL
Table 2-1 lists and briefly describes the operator controls and indicators of the BE1-51/27C Time
Overcurrent Relay with voltage control. Reference the call-out letters to Figure 2-1.
Table 2-1. Controls and Indicators
Letter
Control or Indicator
Function or Indicator
A
TAP NEUTRAL
Selector
Provides selection of the neutral overcurrent pickup
point in conjunction with the front panel
NEUTRAL
CAL
control.
B
PHASE - TAP
Selector
Provides the selection of the overcurrent pickup point
in conjunction with the front panel
TAP CAL
control.
C
CAL NEUTRAL
Control (On
Relays with Phase-and-
Neutral Sensing Only)
A single turn potentiometer provides adjustment of the
neutral overcurrent pickup point between the selected
tap setting and the next lower tap setting.
Not
Shown
TAP RANGE
Plate High/Low
Plate position indicates the terminal connections (high
or low) used to select the current sensing input range.
Refer to Table 2-2 for sensing input ranges.
D
TIME DIAL NEUTRAL
(If
present)
Determines the time delay between sensing of the
overcurrent condition and the closing of the output
relay. Refer to Section 1 and Table 2-3 for curve
selection information.
E
TIMING NEUTRAL
(If pres-
ent)
LED illuminates when the neutral pre-set overcurrent
pickup point is reached and exceeded.
F
Time Current Characteristic
Curve Selector (Z1, Z2, and
Z3 Timing Options Only)
Provides selection of the time current characteristic
curves. Refer to Section 1 and Table 2-3 for curve
selection information. Cutaway view shows switch
behind the front panel.
G
POWER
Indicator
LED illuminates to indicate that the relay power
supply is functioning.
H
Target Reset Lever
Manually resets all targets (both element and function
type).
I
FUNCTION
Targets
TIME
INST1, INST2
*
Front panel
FUNCTION
targets trip when the
corresponding output relay is energized by an
overcurrent condition.
J
ELEMENT
Targets
Front panel
ELEMENT
targets trip when an output
relay is energized by an overcurrent condition.
Summary of Contents for BE-51/27C
Page 1: ...0 1 2 3 4 5 67869 ABC DEF G 6H II GGJ KL M DEF DEK...
Page 16: ...BE1 51 27C Controls and Indicators 2 2 Figure 2 1 Location of Controls and Indicators...
Page 20: ...BE1 51 27C Controls and Indicators 2 6...
Page 22: ...BE1 51 27C Functional Description 3 2 Figure 3 2 Functional Block Diagram...
Page 32: ...BE1 51 27C Installation 4 7 Figure 4 10 Typical Internal Diagram Sensing Input Type L...