Basler 9 1210 00 106 Instruction Manual Download Page 10

3-5

Table 3-1. Voltage Selection Chart.

Voltage Regulator

Model

Voltage Regulator

Rating

MVC Input

Voltage

Voltage Selection

Terminal

KR7F,KR7FF,

SR8A,SR8F

125 V @ 7 A or less

240 Vac

125

SR4A,SR4F,

KR4F,KR4FF

63 V @ 7 A or less

120 Vac

63

XR2001,XR2004

63 V @ 7 A or less

240 Vac

63

KR2F,KR2FF

32 V @ 7 A or less

120 Vac

32

APR63-5

63 V @ 7 A or less

240 Vac

63

APR125-5

125 V @ 7 A or less

240 Vac

125

a. With the AUTO-OFF-MANUAL voltage control mode switch placed in MANUAL, the automatic
voltage regulator is removed from the line and generator output voltage is controlled manually by the
MANUAL VOLTAGE ADJUST control.  When placed in the AUTOMATIC position, the generator
output voltage is controlled by the automatic voltage regulator. Complete excitation shutdown occurs
when the voltage control mode switch is placed in the OFF position.

b. Start the prime mover following the manufacturer's procedure, set the MANUAL VOLTAGE
ADJUST
 control to minimum (counter-clockwise), and place the AUTOMATIC-OFF-MANUAL
voltage control mode switch in MANUAL position.  Note that the voltage may be unstable (hunting) if
the MANUAL VOLTAGE ADJUST control is set below 30 Vac.

c. Allow the generator to build-up and slowly increase the generator output voltage with the MANUAL
VOLTAGE ADJUST
 control until the generator output voltage reaches the desired level.

To verify that the MVC-300 is operating properly, use the following procedure and the connections of
Figure 3-4 for a bench test.  Notice that the voltage regulator is not necessary for this test.

(1) With no power applied to the MVC-300 and all connections to the voltage regulator re-

moved, place the AUTO-OFF-MANUAL voltage control mode switch to the MANUAL posi-
tion.

(2) Connect a 120 Vac 100 Watt light bulb to terminals F+ and F- of the MVC-300, and connect

the jumper to Terminal 63.

3-2. OPERATION

CAUTION

With the voltage control mode switch in either MANUAL or OFF
position, some terminals of the regulator are connected to the
generator and present a potential shock hazard.  No attempt
should be made to remove or troubleshoot the regulator while
the generator is running.

3-3. OPERATIONAL TEST

Summary of Contents for 9 1210 00 106

Page 1: ...ELECTRONIC MANUAL VOLTAGE CONTROL Model MVC 300 Part Number 9 1210 00 106 Publication Number 9 1210 00 993 Date July 1993 Revision F July 1996...

Page 2: ...c Company Highland IL It is loaned for confidential use Subject to return on request and with the mutual understanding that it will not be used in any manner detrimental to the interests of Basler Ele...

Page 3: ......

Page 4: ...switch are provided on the front panel Table 1 1 provides the electrical and physical specifications of the MVC 300 Table 1 1 Specifications Input Power 120 Vac 10 Single Phase 50 320 Hz 240 Vac 10 S...

Page 5: ...build up circuit relinquishes control to the MANUAL VOLTAGE ADJUST control on the front panel c The AUTO OFF MAN voltage control mode switch allows transfer from the voltage regulator to the Manual V...

Page 6: ...3 3 Interconnection Diagram It is imperative that the MVC 300 be connected to provide an output which corresponds to the voltage regulator ratings in order to prevent damage to the MVC 300 or the reg...

Page 7: ...3 2 Figure 3 1 Panel Drilling Template...

Page 8: ...3 3 Figure 3 2 MVC 300 Outline Drawing...

Page 9: ...3 4 Figure 3 3 MVC 300 Interconnection Diagram Typical...

Page 10: ...and place the AUTOMATIC OFF MANUAL voltage control mode switch in MANUAL position Note that the voltage may be unstable hunting if the MANUAL VOLTAGE ADJUST control is set below 30 Vac c Allow the gen...

Page 11: ...UAL VOLTAGE ADJUST control fully counter clockwise CCW Remove the 120 Vac source from Terminals 23 and 24 and select 32 volt operation by moving the jumper to Terminal 32 Apply the 120 Vac source to T...

Page 12: ...ch test procedure Due to a protective coating repair replacement of individual components on the printed circuit board assembly should not be attempted and the complete replacement of the board is rec...

Page 13: ...e does not build up proceed to Step 4 Step 4 Verify that internal fuses F1 and F2 are good If either fuse is defective or blown replace fuse and proceed to Step 5 If both fuses are not defective or bl...

Reviews: