equipment. If a humidity sensor is not being used, the setting should be set to 0 and the controller will 
display a 0% humidity level at all times.  
 

Light (PAR- P

hotosynthetic 

A

ctive 

R

adiation

) Sensor (Optional)  

 

 

The light sensor is used to detect the number of photons arriving in a square meter every 

second.  The photons are measured in micro moles per second per meter squeared. 300-500 is typical 
on a cloudy day. 2000 is high reading on a sunny day.  The WeatherBoss only has a light reading to 
shared with other Bartlett Environmental controllers connected through Radio Link. When connected 
the photo sensor reading can be used to control lighting, shade or misting.  If a light sensor is not being 
used, it can be deactivated by pressing Menu -> Configuration -> Light Sensor Source, select Off, and 

press “

Save

”. 

 

 
 

Manually Activate Alarm 

The 

Force 

button may be pressed at any time to activate the output of the Weather Alarm, this 

is a manual override feature. The Weather Alarm will close any open vents to the first programmed 
position that are programmed to in CIS or Headgrower. The roof vents will remain closed for ten 
minutes or until the 

Cancel or Block 

button is pressed. After ten minutes the roof vents will 

automatically return to being controlled by the environmental controller. The Weather Alarm will return 
to normal operation. When 

Force 

is pressed the Wind A1, Wind A2, and Rain boxes on the main screen 

will turn yellow and read Force.  
 

Block Alarm 

The 

Block Alarm 

button may be pressed at any time to cancel the output of the WeatherBoss, 

this is a manual override feature. The WeatherBoss will allow any roof vents to return to the control of 
the environmental controller.  The roof vents will remain under control of the environmental controller 
for 20 minutes or until the 

Force

 key is pressed. The WeatherBoss will return to normal operation.   

Summary of Contents for WeatherBoss

Page 1: ...8 28 20 1 WeatherBoss Operation Manual BARTLETT Instrument Co 1032 Ave H Fort Madison IA 52627 319 372 8366 www bartinst com...

Page 2: ...MENU SCREEN 5 SETTINGS 5 CONFIGURATION 5 SENSOR READINGS 7 RAIN SENSOR 7 WEATHER SENSOR 7 TEMPERATURE SENSOR 8 HUMIDITY SENSOR OPTIONAL 8 LIGHT PHOTO SENSOR OPTIONAL 9 MANUALLY ACTIVATE ALARM 9 BLOCK...

Page 3: ...e East but a low speed for winds from the West Alarm 2 could be the opposite having a high speed alarm set for wind from the West and low speed alarm from the East This alarm could be assigned to Vent...

Page 4: ...arm is active it will change to either be yellow Force or red Alarm Light Sensor Reading Displays the current light sensor reading in micro moles per second per meter squared Wind A2 Reading Displays...

Page 5: ...the Headgrower cloud platform for remote monitoring and control of the WeatherBoss See the WiFi section for more information about firmware updates WiFi Set up Wi Fi for Firmware download and for rem...

Page 6: ...hannel for the Headgrower app See your Headgrower manual for more information Headgrower ID Displays the HEadgrower ID for your controller This is similar to your controllers serial number and cannot...

Page 7: ...rection if a standard anemometer is being used High Activation Speed If the wind speed is greater than the High Activation Speed the alarm will activate When the alarm activates the environmental cont...

Page 8: ...work provided with your humidity sensor needs to be entered into the WeatherBoss Go to Menu Configuration Humidity Cal and enter the 4 digit code provided and press Save If a humidity sensor is not be...

Page 9: ...larm The Force button may be pressed at any time to activate the output of the Weather Alarm this is a manual override feature The Weather Alarm will close any open vents to the first programmed posit...

Page 10: ...estore factory default settings The default settings are Activation Set Point 20 MPH Drop Out Set Point 15 MPH Activation Delay 4 Seconds Drop Out Delay 6 Seconds Units English Response Time 1 Wind Al...

Page 11: ...peed drops below 15 miles per hour for 6 seconds Activation Set Point 20 MPH Drop Out Set Point 15 MPH Activation Delay 4 Seconds Drop Out Delay 6 Seconds 1 Output Off Wind speed is below the activati...

Page 12: ...ays The WeatherBoss will close any open roof vents to the first programmed position when the when the wind speed exceeds 20 miles per hour The roof vents will return control of the roof vents to the e...

Page 13: ...on set point and the output has not been triggered 3 Output On Wind speed is above the activation set point output triggers immediately 4 Output On Wind speed is below the activation set point and the...

Reviews: