Operation Manual no. BP/IO/21/16 ed. 5.2.1
6
Technical parameters
Table 4: Technical parameters
Technical parameters
DC/AC input power
1
W/VA 50Hz
Rated DC/AC supply voltage
24/42
V
Permitted AC supply voltage
17…53
V
Permitted DC supply voltage
19…75
V
Contacts
2 change-over contacts
Relay mechanical strength
3 • 10
7
Rated load
250VAC 5A
120VAC 3A
240VAC 1,5A
30VDC 4A
120VDC 0,22A
250VDC 0,1A
AC1
AC15
AC15
DC1
DC13
DC13
Open contact insulation strength
1000
V AC/DC
Coil-to-contact insulation strength
5
kV
Ingress protection rating
IP20
Measuring voltage
18 ± 5%
V
Rated network voltage
≤
1140
V AC
Rated frequency of the protected network
50
Hz
Settings range
2…120
kΩ
Leakage stage tripping time (preferred connection layout, see Fig. 4a-
4d, with incremental change of leakage resistance from infinity to 1kΩ
ref. PN-G-42040)
≤
100
ms
Leakage stage tripping time (preferred connection layout, see Fig. 4e-
4h, ref. PN-EN 50628)
≤
200
ms
Additional time delay
0…1,5
s
Return value
min. 30% above the response
threshold
Measuring output (analogue spark-proof)
0…10
V
1
at Ri
min
= 100kΩ
ER 100ims
Page 9