Bartec BCS36x8ex Series Supplementary Description Download Page 3

BCS 36x8

ex

 

Connection to PLC 

 

 

Technical changes reserved. 
04/2019 

3/10 

 

 

1.

 

General information for the connection to PLC 

 
The BARTEC system of the BCS36x8ex series consists of a hand-held scanner (corded or Bluetooth) and an associated 
universal supply module(USM) or base station. 
The hand-held scanner can be connected to a PLC via these associated components. 
 
All used interfaces of the USM (USB, RS232, RS422 and RS485) can be connected to a PLC. 
 
There are a number of different manufacturers for PLCs. The connection of a hand-held scanner depends on the availability 
of an interface to the PLC and the ability of the PLC to process the incoming data. The PLC must support the open ASCII 
protocol. 
 
There is no compatibility list existing. 
The following must be observed when connecting the handheld scanner to a PLC: 

 

What interfaces are available on the PLC/PLC?  
The USM supports the following interfaces. 

-

 

USB-SPP (virtual serial interface) 

-

 

RS232 

-

 

RS422 

-

 

RS485 

 

The PLC supports the open ASCII protocol. 

 

What interface parameters are set on the PLC? 
All interconnected components must be set to the same parameters. Otherwise, the communication can not work 
correctly or not at all. 

-

 

Baud Rate 

-

 

parity 

-

 

Stop Bit 

-

 

Data Bit 

-

 

Hardware/Software Handshaking 

 

 

The way of processing the data at the PLC and what has to be set at the scanner is the responsibility of 
the plant operator. 
E.g. a serial interface has no intelligence of its own and cannot process incoming data independently. This 
means that the controller must monitor the serial interface and process incoming data (read/write routine).

 

 
 

 

Summary of Contents for BCS36x8ex Series

Page 1: ...ernet www bartec de Supplementary description Translation of the original Addendum to user manual 11 A1S4 7D0001 BCS36x8ex Series Type 17 A1S4 HP ATEX IECEx Zone 1 21 CSA Class I II III Division 1 Typ...

Page 2: ...al information for the connection to PLC 3 2 Connection to PLC 5 3 Sample Project for Siemens Simatic S7 300 5 3 1 Sample project 6 3 2 Hardware Configuration 6 3 3 Software Configuration 7 3 4 Projec...

Page 3: ...otocol There is no compatibility list existing The following must be observed when connecting the handheld scanner to a PLC What interfaces are available on the PLC PLC The USM supports the following...

Page 4: ...e 1 Availability on the PLC side Communication controller processor CP Open ASCII driver Solution 2 availability on the PROFIBUS DP side Figure 2 Availability on the DP side PROFIBUS DP converter to s...

Page 5: ...3 Sample Project for Siemens Simatic S7 300 A sample project is available for a Siemens SIMATIC S7 300 with CPU 315 2 PN DP central processing unit The project is available as a download on the BARTEC...

Page 6: ...p file Can be opened by using the Siemens software can be found under the TAB Project and navigate to Project and Retrieve 3 2 Hardware Configuration The sample project Test Scanner 01 zap15 is create...

Page 7: ...reserved 04 2019 7 10 3 3 Software Configuration It s important to know that the serial interface parameters on all connected devices are identical Setup Right click on the CPU 315 2 PN DP Properties...

Page 8: ...BCS 36x8ex Connection to PLC 8 10 Technical changes reserved 04 2019 3 4 Project tree for necessary modules The project tree shows all the necessary modules...

Page 9: ...ection to PLC Technical changes reserved 04 2019 9 10 3 5 Main OB1 In OB1 with command call the routine for receiving of data is started 3 6 Function FC7 RCV_RS232C The function FC7 control the handli...

Page 10: ...arcode data Status Feedback from the module according to Siemens Barcode Scanner 0 25 Data defined as CHAR Length can free defined In sample 0 25 End of String End character In this sample defined as...

Reviews: