BARRON EXITRONIX VEX-S Series Installation Instructions Download Page 2

8. Make electrical connections: see Electrical Connection sections.  

9. Mount the sign to the junction box with (2) #8-32 screws (provided) and tighten securely.

 

10. Remove the chevron(s) from the EXIT legend(s) if necessary.

11. Attach the battery jumper wire (for battery backup unit) to the PC board only after continuous AC power can be    

      supplied to the unit.  

12. Slide the faceplate back into place and replace the screw. 

Wall Mounting

1. Remove the faceplate by removing the screw from the bottom of the unit, then slide the faceplate down and set 

    aside.

2. Remove knockouts from the backplate that match the junction box. 

3. Route the units input wires through the center wire access hole of the backplate and make the wiring connections.

4. Make electrical connections: see Electrical Connection sections.   

5. Push the wires against the back of the sign to minimize any chance of the wires interfering with the illumination of 

    the letters.

6. Mount the sign to the junction box with (2) #8-32 screws (provided) 

    and tighten securely. 

7. Remove the chevron(s) from the EXIT legend(s) if necessary.

8. Attach the battery jumper wire (for battery backup unit) to the PC board. 

9. Slide the faceplate back into place and replace the screw.

Electrical Connections 

All electrical connections should be made inside the junction box.

    

    Make Electrical Connections as follows:

120V AC                         277V AC

White - Common            White - Common

Black - 120VAC              Red/Orange - 277VAC

Green - Ground              Green - Ground

      

    Note:

 Cap unused leads to prevent shorting.

800.533.3948 • www.barronltg.com 

2

INSTALLATION INSTUCTIONS

10070182 Rev 3 - 02/19

 VEX-S SERIES

Battery Backup

AC Only