Self-Test/Self-Diagnostics (G2)

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the emergency unit. At 

predetermined intervals, the emergency unit will automatically switch into battery mode. Refer to the 

Self-Test Feature

 

section below for timing details. The emergency unit will also perform various Self-diagnostic tests to determine if there 

are any faults. Visual signaling will alert maintenance personnel to a fault of the emergency unit electronics, battery, 

and/or battery charger. The circuitry continuously monitors the operating condition of the emergency unit and battery 

charging circuit/battery supply voltage. Refer to the 

LED Indicator

 section below for fault reporting details.

Self-Test Feature

• The emergency unit will automatically switch to battery mode every month for a period of 1 minute.

• The emergency unit will automatically switch to battery mode every 6 months for a period of 30 minutes.

• The emergency unit will automatically switch to battery mode every 12 months for a period of 90 minutes.

LED Indicator

Once the unit is properly installed according to the installation instruction sheet and AC power is supplied, the unit will turn 

on and the Self-diagnostic test function will initiate. After this, the bi-color LED will indicate the status of the unit.

• A steady green LED indicates that normal AC power is being supplied to the emergency unit and the battery is 

charged.

• A blinking green LED indicates that the unit is in battery mode. Refer to the 

Test Button Feature 

section below for 

manual test details.

• A red LED indicates whenever the Self-diagnostic system has detected a fault condition. Refer to the chart below to 

determine the fault condition:

Test Button Feature

MANUAL TEST – Pressing the test button will switch the unit into battery mode for a set amount of time. The desired 

length of the test is determined by the number of times the test button is pressed.

• Pressing the test button once will switch the unit into battery mode for a period of 30 seconds.

• Pressing the test button twice within 2 seconds will switch the unit into battery mode for a period of 3 minutes.

• Pressing the test button 3 times within 2 seconds will switch the unit into battery mode for a period of 30 minutes.

• Pressing the test button 4 times within 2 seconds will switch the unit into battery mode for a period of 90 minutes.

RESET – Pressing and holding the test button for 2 seconds will reset the LED to a steady green. If multiple faults are 

present, it may be necessary to repeat this procedure for each remaining fault indicated by the blinking red LED.

Use in accordance with local building codes.

Red LED Indication

Blinking 1 Time

Blinking 2 Times

Blinking 3 Times

Blinking 4 Times

Blinking 7 Times

Unit Fault

Battery is Disconnected

Battery Failure

Charger Board Circuit Fault

Transfer Function Failure

LED Strip Fault

Corrective Action

Check Battery Connection

Check Battery Then Consult Factory
Check Battery Then Consult Factory
Check Battery Then Consult Factory
Check Battery Then Consult Factory

10070149 

R

EV 4 - 04/22

5

800-533-3948 www.barronltg.com

NY900U Series

Installation Instructions

Summary of Contents for Exitronix NY900U Series

Page 1: ... locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than intended use Allow battery to charge for 24 hours before first...

Page 2: ... the correct orientation Fig 3 9 Peel off the appropriate chevrons from the EXIT panel as desired 10 Snap the front cover back into place 11 Rotate the EXIT panel as needed for the mounting application The EXIT panel can rotate from 0 to 180 Fig 4 End Mount 1 Follow steps 1 and 2 in the Surface Ceiling or Surface Wall Mount section 2 Remove the hole plug from the end cap 3 Secure the canopy to the...

Page 3: ...ure the hanger bars are positioned correctly Use the adjusting screws to guide the hanger bars The bottom of the recessed housing should be level with the bottom of the joist Secure temporarily by hammering in the nail in tabs then permanently with nails Fig 9 10 Adjust the height of the recessed kit as needed then tighten all screws to secure the adjusting bracket and hanger bars 11 Make electric...

Page 4: ...nt applications rotate the EXIT panel 90 Fig 12 Electrical Connections All electrical connections should be made inside the J box Make electrical connections as follows Fig 13 120VAC 277VAC White Common White Common Black 120VAC Orange 277VAC Green Ground Green Ground Note Cap unused leads to prevent shorting Fig 11 Test Switch Connector LED Indicator Test Switch Trimplate Trimplate Screws Fig 12 ...

Page 5: ... the unit is in battery mode Refer to the Test Button Feature section below for manual test details A red LED indicates whenever the Self diagnostic system has detected a fault condition Refer to the chart below to determine the fault condition Test Button Feature MANUAL TEST Pressing the test button will switch the unit into battery mode for a set amount of time The desired length of the test is ...

Reviews: