background image

NFT Series

Installation Instructions

10070187  REV 4 - 07/19

   2

800-533-3948 www.barronltg.com

Wall/Ceiling Mount - Back Power Feed

1. Insert a flat blade screwdriver into the two slots to remove front cover 

    from backplate. (Fig 1).

2. Remove knockout from center of backplate and route wires through the 

    hole.

3. Remove appropriate knockouts on backplate and mount to junction box.

4. Connect the fixture wires to the power supply wires using the wire nuts 

     provided. Connections should be made inside junction box. Connect the 

     white wire to neutral and black wire to the hot lead. Refer to 

Wiring  

     Diagram

 section.

5. Connect remote lamp wires if fixture is remote capable. Refer to 

Remote 

     Lamp Connection

 section

.

6. Connect battery to PCB.

7. Snap the front cover on the backplate.

8. Restore power and then test fixture by pressing test button. LED heads 

    will turn on.

9. Adjust the direction of lamp heads for optimal lighting coverage.

Wall Mount - Top Power Feed

1. Insert a flat blade screwdriver into the two slots to remove front cover 

    from backplate. 

2. Remove top knockout on the top flange of fixture for the flexible conduit 

    access hole.

3. Secure flexible conduit to access hole and route wires through conduit 

    to junction box. (Fig. 3)

4. Remove appropriate knockouts from backplate and mount to wall.

5. Connect the fixture wires to the power supply wires using the wire nuts 

     provided. Connections should be made inside junction box. 

     Connect the white wire to neutral and black wire to the hot lead. 

     Refer to 

Wiring Diagram

 section.

6. Connect remote lamp wires if fixture is remote capable. 

    Refer to 

Remote Lamp Connection 

section.

7. Connect battery to PCB.

8. Snap the front cover on the backplate.

9. Restore power and then test fixture by pressing test button. 

    LED heads will turn on.

10. Adjust the direction of lamp heads for optimal lighting coverage.

Open Fixture

Use Screwdriver

to Pry Open

Mounting 

Screws

Backplate

Battery 

Connector

Front 

Cover

Wall Mount - Back Power Feed

Fig. 2

Fig. 1

Wall Mount - Top Power Feed

Fig. 3

Flexible

Conduit

Junction Box

Wire Nuts

Mounting 

Screws

Summary of Contents for Exitronix NFT Series

Page 1: ...Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than intended use...

Page 2: ...t Top Power Feed 1 Insert a flat blade screwdriver into the two slots to remove front cover from backplate 2 Remove top knockout on the top flange of fixture for the flexible conduit access hole 3 Secure flexible conduit to access hole and route wires through conduit to junction box Fig 3 4 Remove appropriate knockouts from backplate and mount to wall 5 Connect the fixture wires to the power suppl...

Page 3: ...ctor 2 Plug the remote male connector into the female connector 3 Connect extended remote head wires to the remote wires using wire nut Yellow positive Purple negative Fig 4 Female Connector Ground Male Connector Fig 5 Extended Remote Wires Remote Wire Wire Nut Female Connector Remote Male Connector AC INPUT White Neutral Black 120 277VAC Integral LED Head Remote Heads Option Battery ...

Page 4: ...AUTION After solving the fault of emergency equipment please press test button for 2 seconds without releasing to reset LED indicator will show green 3 For manual test press test button as follows One blink ON pause for 4 seconds Battery is not connected Two blinks ON pause for 4 seconds Battery is shorted or battery voltage drops below acceptable level Three blinks ON pause for 4 seconds Charger ...